1
Input
Local control input, triggered by applying voltage to terminals 1-2.
Triggering the input causes the relay contact to close for the time
the button is pressed.
Attention!
The control input does not work with illuminated buttons.
2
3
Output
Relay output - separated normally open contact (the contact
closes when the local button or the button on the transmitter
associated with the controller is pressed).
Attention!
In the case of integration with a gate automatics system, termi-
nals 3-4 must be connected in the place provided on the gate
control unit for the connection of the local control "open/close".
4
5
Supply
Controller power supply
Polarity of the power supply (order of connecting the wires from
the power supply to terminals 5-6) - arbitrary.
6
Load capacity
8 A/250 V AC (AC-1)
The actual maximum load depends on the natu-
re and design of the receiver.
For more information visit: www.fif.com.pl.
Programming description
The receiver can be associated with 32 remote buttons.
If the same transmitter button is programmed more than once, it will only be
stored once in the controller's memory.
Adding the 33rd (and subsequent) remote buttons will erase the first of the
programmed transmitters from memory.
If no action is performed by the user in programming mode for 30 seconds
(e.g. pressing the PROG button or linking a transmitter button to the receiver),
the programming mode will be terminated.