A diagram of how the relay works is shown in the figure below:

The relay is equipped with thermal protection to prevent 

the device from exceeding a safe internal temperature 

(e.g. due to excessive load current). If this is triggered, 

the internal relay switches off and the display shows the 

message:

The condition for returning to normal operation is:

– the temperature inside the enclosure decreases to a 

safe level,

– 10 minutes have elapsed since the temperature drop-

ped (this state is signalled by alternating display of an 

error message and the time remaining until the alarm 

is cancelled).

Содержание CP-721-FPV

Страница 1: ...reases Precise adjustment of switching voltage Programmable delay for relay activation and deactivation Programmable voltage hysteresis for relay deactivation Direct control of loads up to 16 A LED display for continuous voltage monitoring Purpose Functions F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif co...

Страница 2: ...ltage time countdown starts If the voltage is exceeded for a time longer than the pre set Uon value the built in relay will switch on Activation of the relay is signalled by lighting up the yellow LED located below the display The condition for switching off the relay is that the mains vol tage drops below the value Uon hys while this voltage must remain below the preset level for the time set in ...

Страница 3: ...ssive load current If this is triggered the internal relay switches off and the display shows the message The condition for returning to normal operation is the temperature inside the enclosure decreases to a safe level 10 minutes have elapsed since the temperature drop ped this state is signalled by alternating display of an error message and the time remaining until the alarm is cancelled ...

Страница 4: ... the user Parameter Function Settings Min Max Step Relay activation voltage 245V 265V 1V Relay deactivation voltage hysteresis 1V 10V 0 5V Delay from overvoltage to relay activation 0s 999s 1s Delay from voltage drop to relay deactivation 0s 999s 1s Settings ...

Страница 5: ...eter to be edited Uon Use the or buttons to select the correct parameter and press both buttons simultaneously once more until the value of the edited parameter is displayed Use the or buttons to set the new value of the parameter Confirmation of the new value takes place after pressing both buttons simultaneously or after leaving the entered value unchanged for a few secondsd Change of settings s...

Страница 6: ...tal lations it is recommended to connect the CP 721 FPV relay to the phase with the highest voltage overshoot or to use a separate relay for each phase and control the load via an additional phase switch An example wiring diagram is shown in the figure below ...

Страница 7: ...C 1 16A contact activation voltage 245 265V step 1V contact deactivation hysteresis 1 10V step 0 5V contact activation delay 0 999s step1s contact deactivation delay 0 999s step 1s measurement accuracy 1V display 3 segment LED 5 9mm power indication yellow LED power cinsumption 0 8W terminal 2 5mm screw terminals cord 4 0mm screw terminals wire tightening torque 0 5Nm working temperature 25 50 C d...

Страница 8: ...p j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which conformity is declared can be found at www fif com pl on the product page Warranty CE declaration E220816 ...