background image

Fancom VLR.6 

2. Technical specifications

2

2.

 

Technical specifications

Power supply

Mains voltage

230Vac (-10%  +6%)

or 115Vac (-10%  +6%)

by power supply selection

Mains frequency

50-60Hz

Power consumption ( of VLR.6)

3.5VA

Max. current output

6A

Fuse (dimensions 6.3×32mm)

Very Fast Acting 10A - 250V

Power outage relay

Relay de-energizes if the power fails

30Vac/60Vdc - max. 2A

Control

Type

10-0Vdc/0-10Vdc

Input resistance

120k

Manual operation

Knob

for 0-100% if the 10-0Vdc control fails

Switch

for “man-0-aut” (man = directly on mains)

Housing

Plastic housing with screw on lid

IP54

Dimensions (l×w×h)

180×240×140 (7.1×9.4×5.5 inches)

Weight (unpacked)

1.9kg(4.2lbs)

Ambient climate

Operating temperature range

0

°

C to +40

°

C (32

°

F to104

°

F)

Storage temperature range

-10

°

C to 50

°

C (14

°

F to 112

°

F)

Relative humidity

< 95%, uncondensed

!

Fancom advises 2-wire connection of Fancom fans. If the fans are
connected parallel, heat production per fan may increase (causing
a shortened working life). Fancom therefore advises not to parallel
switch more than three fans. See connection diagrams.

Содержание VLR.6

Страница 1: ...VLR 6 MANUAL GB US CA...

Страница 2: ...s of this manual However should any errors be detected Fancom would greatly appreciate being informed of them The above notwithstanding Fancom can assume no responsibility for any errors in this manua...

Страница 3: ...ard NEN EN 50082 1 and the surge immunity standard NEN EN IEC 61000 4 5 4kV common mode and 2kV differential mode The low voltage guide according to NEN EN IEC 60950 Satisfies the conditions set out i...

Страница 4: ...2 Technical specifications 2 3 Mounting and installation 3 4 Operation 4 5 Points of attention 5 5 1 Analog control 5 5 2 Jumper setting 6 6 Adjustment procedures 7 6 1 Fan without DSR feedback 7 6 2...

Страница 5: ...e any questions please do not hesitate to contact your Fancom dealer The subjects discussed in this manual are listed in the table of contents The following symbols are used in this manual Suggestions...

Страница 6: ...VLR 6 is a power controller for the control of 1 phase voltage controllable triac fans Electronically controllable lighting incandescent lighting and controllable fluorescent lighting Heating lamps ph...

Страница 7: ...ation Knob for 0 100 if the 10 0Vdc control fails Switch for man 0 aut man directly on mains Housing Plastic housing with screw on lid IP54 Dimensions l w h 180 240 140 7 1 9 4 5 5 inches Weight unpac...

Страница 8: ...t influence not in the sun not in places where the temperature can rise sharply etc 3 Never mount the end station in a room where animals are present because of the manual control 4 Mount the end stat...

Страница 9: ...g the switch and knob on the front Table 1 indicates the function of the output at the different switch and or knob settings Switch Knob man 0 aut man aut Table 1 Operation Switch Knob Output aut aut...

Страница 10: ...to a 0 10Vdc control jumper J3 should be changed see jumper setting The manual operation connection should also be changed This means that the red RD and blue BL wire should be changed around Fancom a...

Страница 11: ...efore setting the jumper s Table 3 Jumper table Jumper setting Application J1 J2 J3 J4 Fan without DSR feedback Place with small fan 35 and 40 Jumper is in small bag in lid preferably 10 0Vdc V Fan wi...

Страница 12: ...he fan starts running 8 Using potentiometer P2 adjust the minimum voltage between U and V so that the fan is barely running A Fancom fan is normally 2 wire connected and the voltage between U and V no...

Страница 13: ...urn until the fan starts running 8 Using potentiometer P2 adjust the minimum voltage between U and V for a Fancom fan not below 30Vac 6 3 Lighting 1 Switch off the power supply to the end station 2 Co...

Страница 14: ...period controlled control within 10 seconds This means for example that with 40 control the heating will be on for 4 seconds and off for 6 seconds A full period control means that an entire sine will...

Страница 15: ...cations reserved Only for US and Canada models 230V 115V POWER SUPPLY SELECTION 230Vac 115Vac L2 T2 T2 T1 L1 F2 Power outage relay contact Alarm unit max 30Vac 60Vdc max 2A IMPORTANT the power failure...

Страница 16: ...AS 5 Fancom bv agro computers 4 3 2 1 L2 A2 L1 A1 C1 C2 man aut L N Z U V man aut d d 10 06 97 Doc no 03 01 9723 02 Connection VLR 6 ELECTRICAL DIAGRAM VLR 6 Technical modifications reserved Knob GR R...

Страница 17: ...r min max thermostat ALARM DIAGRAM WITH A MULTIPLE ALARM UNIT alarm per section Fancom multiple alarm unit Siren 12Vdc Fancom advises you to install a min max thermostat in each CLIMATE room house and...

Отзывы: