12
EXTERNAL ROOF SOLUTION - TILE ROOF INSTALLATION
Inspection:
Ensure the unit has arrived in good condition and that the impeller will spin freely.
This product is designed to be installed on a roof up to 45° pitch.
1. Installation of this product should be carried out by appropriately qualified persons.
2. Prepare an opening in the tiled roof 220 mm minimum (with regard to roof pitch angle)
diameter. The hole should be positioned adjacent to a rafter or other member to facilitate
the use of the mounting brackets (optional accessory).
3. Cut a 190 mm diameter hole in the rubber roof flashing (optional accessory) for fitting
over the rigid duct.
4. Slide the flashing over the rigid duct to the required position.
5. Check the fit of the duct in the cut hole. The duct must be positioned vertically.
6. If satisfactory fasten the duct to the rafter or other support using the mounting brackets
(optional accessory).
7. Fit the upper edge of the flashing underneath the tile, bending over top edge to form an
anti-capillary barrier.
8. Cut two tabs in the corners of the lower section and turn under tile (refer detail). Lay
the lower section of the flashing over the tiles and form a run off tray. Form to tiles as
required.
9. Attach the flexi duct leading from the rangehood to the bottom of the rigid duct using
the supplied duct clamps. (purchased separately ) can be used if necessary if the duct run
has been extended.
10. Connect the male power plug to the female plug connected to the rangehood. An ex-
tension lead (purchased separately ) can be used if necessary if the duct run has been
extended.
Safety Considerations:
1. All connections must be in accordance with any local regulations.
2. Fans have automatic thermal cut out switches incorporated in the motor as standard.
3. This product is not intended for use by persons (including children) with reduced sensory
or mental capabilities, or lack of experience and knowledge, unless they have been given
supervision or instruction concerning use of the product by a person responsible for their
safety. Children should be supervised to ensure that they do not play with the product.
4. For duct or partition mount, precautions must be taken to avoid the back-flow of gases
into the room from the open flue of gas or other open-fire appliances.
5. If the supply cord is damaged it must be replaced by the manufacturer, its service agent
or similarly qualified persons in order to avoid a hazard.
EXTERNAL WALL SOLUTION
Inspection:
Ensure the unit has arrived in good condition and that the impeller will spin freely.
Installation:
1. Installation of this product should be carried out by appropriately qualified persons.
2. This fan is designed for connection to 200 mm duct using duct tape or clamps.
3. Cut either a circular or square hole in the wall between 210-240 mm diameter/ square.
Ensure a clean edge.
4. Check the fit of the duct (and clamp if used) in the cut hole. The duct must be positioned
horizontally through the hole.
5. Fit the foam sealing tape supplied to rear of fan housing. Run tape around the outside of
the four mounting holes and ensure the tape join is along the bottom of the housing for
effective seal.
6. Remove cover from fan by un-doing the side fixing screws.
7. Position the fan on the wall with the airflow arrow pointing down.
8. Use fan for template to mark and drill holes for power cable and fastening screws.
9. Pull power cable through assigned hole and attach the flexi duct leading from the range-
hood to the spigot using the supplied duct clamps.
10. Fix fan to wall with appropriate fastening screws.
11. Connect the male power plug to the female plug connected to the rangehood. An ex-
tension lead (purchased separately) can be used if necessary if the duct run has been
extended.
Safety Considerations:
1. All connections must be in accordance with any local regulations.
2. Fans have automatic thermal cut out switches incorporated in the motor as standard.
3. This product is not intended for use by persons (including children) with reduced sensory
or mental capabilities, or lack of experience and knowledge, unless they have been given
supervision or instruction concerning use of the product by a person responsible for their
safety. Children should be supervised to ensure that they do not play with the product.
4. For duct or partition mount, precautions must be taken to avoid the back-flow of gases
into the room from the open flue of gas or other open-fire appliances.
5. If the supply cord is damaged it must be replaced by the manufacturer, its service agent
or similarly qualified persons in order to avoid a hazard.
FLEXIBLE DUC T
FIT GROMME T
S UPPLIED
FIT MOUNTING
BRA CKE TS
TILE FLASHING
SO AKER RUN-OFF
PO WER CA BL E
ø403 / 44 5
ø194 DUCT
ANTI-C APILLA RY
FO LD
597.5 / 599
133 / 154
ER-765/1140 Dimensions
ER-2010 Dimensions
ø197
flexible
duct
Air
behind (included)
Wall
210-240
Содержание Treviso 90
Страница 1: ...INSTALLATION MANUAL falmecau com Treviso 90...
Страница 4: ...4 260 max 1079 263 60 519 max 500 898 490 133 2 200 TREVISO 90 FP5TV90S2...
Страница 15: ...15 NOTE NOTES...