background image

CHAPTER

CHAPTER

5

5

COMMUNICATIONS INTERFACES

RS-232 INTERFACE

15

  Pin # 

Function explanation 

I/O 

RS 232 Rx 

INPUT 

RS 232 Tx 

OUTPUT 

Ground 

 

Location:

The RS-232 interface is standard on all SG series UPS models. The port is 
located on the UPS rear panel, via a DB-9 female connector. 

Supported Protocols

UPSILON 2000 & SEC Smart Mon

BAUD RATE ------- 2400bps
DATA LENGTH---- 8 bits
STOP BIT----------- 1 bit
PARITY-------------- None

DB-9 Connector Pin Assignment

When making a connection between a computer and the UPS RS-232 port, 
always use the green cable supplied with the UPS due to the propriatary pin-
out of the RS-232 port.

There are communications options that WILL DISABLE the RS-232 port and 
render it inoperable. The options are as follows:

a.

Internal SNMP/HTTP agent option installed into the UPS 
communications option slot.

The following options WILL NOT affect the operation of the RS-232 port:

a.

Falcon Opto Coupler based signal interface board installed in the 
communications option slot. 

b.

Any Falcon relay based, dry contact signal interface board 
installed in to the communications option slot.

DB-9 Signals are not isolated and intended for connection to like RS-232 
interfaces. DO NOT APPLY ANY OTHER VOLTAGES TO THESE PINS!

 

 







TX

 

RX 

GEN

 

CAUTION

CAUTION

CAUTION

GND

All manuals and user guides at all-guides.com

Содержание UPS Plus SG Series

Страница 1: ...reserved All other brand names and trademarks are the property of their respective owners The information stated in this document is subject to change without notice 2007 03 20 Falcon Falcon Electric...

Страница 2: ...ion Description 10 Audible Alarms 12 Category One Alarms 12 Category Two Alarms 12 Chapter 4 Front Rear Panel Details 13 Front Panel Overview 13 SG1KRM 1TU Rear Panel Overview 13 SG1KRM 2TU Rear Panel...

Страница 3: ...erior Brownout Surge and Transient Protection Internal System Bypass Eliminates Generator Frequency Voltage Drift Microprocessor Control RS 232 Communications UPSILON Monitoring Shutdown Software Opti...

Страница 4: ...wledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When replacing the UPS batteries use the same number and type of batteries Allow at least 24 hours...

Страница 5: ...Series UPS incorporates advanced microprocessor technology This technology makes possible a high level of internal UPS control and management With the supplied UPSILON software all SG Series UPS mode...

Страница 6: ...time of order verify for proper configuration 3 RACKMOUNT UPS MOUNTING INSTRUCTIONS IMPORTANT a NEVER MOUNT THE UPS OR ANY ASSOCIATED BATTERY BANKS USING ONLY THE FRONT PANEL MOUNTING EARS AS DAMAGE...

Страница 7: ...voltage This will assure a close matching voltage in the event the UPS is placed on bypass b Dip switch 3 enables or disables the Green Mode function The UPS is shipped from the factory with the switc...

Страница 8: ...battery fuse 8 If additional extended battery modules are to be installed perform the following a Perform the preperation outlined in preceding paragraphs 3a 3b abd 3c b Connect the supplied battery i...

Страница 9: ...ollowed by the bypass LED and after several seconds the inverter LED 13 Turn on the connected equipment and verify the UPS does not go into overload by observing the front panel load indicator LEDs 14...

Страница 10: ...for each module All 1kVA UPS models will only require one slide kit Slide Installation Instructions NOTE Only use the referenced lenght screws when mouning the slides to the sides of the UPS and batt...

Страница 11: ...25 Min 300 Min RUN TIME 500W 24 Min 55 Min 95 Min 135 Min 180 Min RUN TIME 700W 17 Min 40 Min 70 Min 100 Min 140 Min RUN TIME 1000W 11 Min 25 Min 42 Min 60 Min 80 Min RUN TIME 1400W 7 Min 16 Min 26 Mi...

Страница 12: ...the battery level is above the low battery warning Level The first LED is lit when the battery level is above the battery cutoff voltage 3 LINE SITE WIRING FAULT INDICATOR LED For models configured fo...

Страница 13: ...s the different modes of operation for this button a Depressing this button when the UPS is off and the utility voltage is not present or with the UPS input circuit breaker in the off position will ca...

Страница 14: ...rating range SG UPS OUTPUT VOLTAGE IS OUT OF PROPER RANGE b Four short beeps indicate the SG UPS output frequency is out of proper operating range The UPS must be repaired SG UPS OUTPUT FREQUENCY IS O...

Страница 15: ...Fan RS 232 Port Output Receptacles 4 IEC320 Power Cord Inlet 200 240Vac only Output Voltage Select Switch Battery Fuse 30A Extended Battery Connector Primary Battery Inside UPS shown with cover plate...

Страница 16: ...acles Primary Battery Connector shown with cover plate removed Cooling Fans RS 232 Port Output Receptacles 4 IEC320 Power Cord Inlet 200 240Vac only Output Voltage Select Switch Output Fuse Primary Ba...

Страница 17: ...e propriatary pin out of the RS 232 port There are communications options that WILL DISABLE the RS 232 port and render it inoperable The options are as follows a Internal SNMP HTTP agent option instal...

Страница 18: ...ommon only PIN JUMPER ASSIGNMENT FOR THE FALCON UA88374 RELAY OPTION BOARD no on bypass signal PIN JUMPER ASSIGNMENT FOR THE FALCON UA88376 RELAY OPTION BOARD with on bypass signal DB 9F PIN JUMPER AS...

Страница 19: ...n for pins 2 3 5 5 Low Battery N O Closes at low battery 6 Remote Shutdown Applying a 5 12Vdc voltage level for 500ms while the UPS is on battery will shutdown the UPS 7 Not Used 8 Not Used 9 Not Used...

Страница 20: ...see page 20 for contact information Never attempt to service batteries High voltage exists within the unit which could cause electrical shock Servicing of batteries should be performed or supervised...

Страница 21: ...cause interference to radio and television reception All models covered in this manual have been tested and found to comply with the limits for a Class A computing device in accordance with the specif...

Страница 22: ...d when returning any SG Series product Falcon Electric will not assume any responsibility for shipping damage In the event of shipping damage you will be notified of the damage and be instructed to fi...

Страница 23: ...OF MERCHANTABILITY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE FOR THIS PRODUCT AND THE USER AGREES THAT IN...

Страница 24: ...oling Low Velocity Forced Air Fans Audible Noise 1 Meter 55dBA Controls and Indicators LED Line Inverter Battery Reserve Load Bypass Alarm Crest Battery Load Capacity Level Audible Alarms DC Mode Low...

Отзывы: