If the CAC line is not connected, the Falcon Hybrid should not
be programmed to send AC Failure or Restoral Signals.
The AC Failure and AC Restore signals have a programmable
delay (default set at 1 minute) in order to prevent false triggers.
3.1.4 Dry Contact Inputs
The dry contact inputs can be used to detect alarms generated
from the outputs of the alarm panel or from other sources.
If the external device generates the alarm by pulling the input to
ground (negative trigger), the pull-up jumper should be inserted
on the input of the Falcon Hybrid.
3.1.5 Contact ID Inputs
The Falcon Hybrid can 'intercept' signals sent by the alarm panel
on its telephone line (Contact ID) interface.
If the Contact ID interface is to be used, the alarm panel's TIP
and RING lines should be connected to the TIP and RING lines
on the Falcon Hybrid.
The alarm panel must be programmed to use its dialer, and the
option for reporting must be set to Contact ID. Refer to the
programming manual of the applicable alarm panel.
I
Falcon Hybrid Installation and Operation Manual
11