8.1 FN -2TXI Model Internal Battery Pack Replacement
8.2 How to Replace the Internal UPS Battery Packs
1
.
Remove the (3) screws securing the lower UPS front panel. Screws are located on the bottom
of the lower front panel.
2.
Lay the panel and screws aside for reassembly.
3.
Loosen and remove the screws securing the (5) battery pack hold down brackets. Lay them aside for
reassembly.
4.
Unplug all (5) of the battery pack interconnect connectors. Note the location of the connector for each
battery pack.
5.
Grasp each of the battery packs, and pull them out of the front of the unit.
6.
Unpack the new battery packs. Take care not to destroy the packaging. Compare the new and old
battery packs and verify that they are the same type. If so, proceed with the next step, otherwise stop
and contact Falcon Service.
7.
Line up and slide in the new replacement battery packs in the correct orientation.
8.
Gently push the battery pack back into the cabinet. Ensure it is tightly seated into the unit.
9.
Reconnect all (5) of the battery pack interface connectors to the correct mating connector on the UPS
chassis.
10.
Reinstall the battery hold-down brackets with the screws originally removed.
11.
Reinstall the front panel to the unit with the screws originally removed.
12.
Perform a UPS self-test immediately upon restarting the UPS.
39
Содержание FN3K-2TXI
Страница 14: ...4 6 Rear Panel Details 14...
Страница 47: ...FN SeriesTM UPS PLUS 5kVA 20kVA 47...
Страница 48: ...48 FN SeriesTM UPS PLUS 6kVA 24kVA...
Страница 49: ...49 FN SeriesTM UPS PLUS 8kVA 32kVA...