6.7 How to Change the Programmed Settings
Note: The UPS must be placed into Off / Bypass mode prior to attempting to change the
following parameter settings.
1. To enter programming mode depress the “On” and “Next Page” buttons at the same time and hold
them down until the UPS sounds two beeps. The audible alarm status parameter setting will be
displayed.
30
The audible alarm parameter
settings cannot be set in this
programming mode.
Depress the “Next Page”
button.
Self-test parameter settings
cannot be set in this
programming mode. Refer to
section 6 of this manual for
setup instructions.
Depress the “Next Page” button
and go to the next page.