33
The next parameter displayed
shows the UPS unit address.
If only one UPS is being used,
the address should be set to
“d0” as shown.
If multiple parallel UPS units are
connected in a parallel
configuration of up tp 40kVA or
up to 30kVA N+1 operation, the
units would be addressed
“id01”, “id02”, “id03” and
“id04”. See the parallel mode
configuration section on pages
16 and 42 of this manual for
more details.
To change between these
settings, depress the “Previous
Page/Change Setting” button.
Repeat pressing the button until
the desired address
setting is displayed.
Depress the “Next Page” button.
The next parameter displayed
defins when the UPS is used in
a parallel configuration. The set-
tings are “P01” and “P02”, If
only one UPS is being
configured (not paralleled), the
position should be set to “P01”
as shown. If UPS units are
connected in parallel it should
be set to P02.
To change between these
settings, depress the “Previous
Page/Change Setting” button.
Repeat pressing the button until
the desired UPS position
setting is displayed.
Depress the “Next Page” button.
At the end of the parameter
setup mode, you will be prompt-
ed to save the settings.
To save the settings press the
“Confirm” button. If you do not
wish to save the settings, press
the Off / Bypass button for five
seconds. The LCD will display
OFF to indicate the
settings are not saved.
X
IMPORTANT: The UPS must be switched to maintenance bypass mode, shut down and restarted after entering
the programming mode.