background image

CHAPTER 6

CHAPTER 6

Maintenance & Technical Support

1.

Care & Maintenance

Falcon

®

ED Series are designed to be maintenance-free.  

They can be cleaned with a damp cloth or non-abrasive cleanser, providing the 
ED is turned off and the input plug is disconnected from the utility source.
On a regular basis, check the vents to make sure they are kept free from 
accumulation of dust, dirt or lint.

2.

Battery Life vs. Temperature (Units supplied with batteries only)

For full battery life, keep the ED close to an ambient temperature of 77ºF. 
The batteries should never be exposed to temperatures below 40ºF and above 
104ºF
.

3.

Battery Replacement (Units supplied with batteries only)

This unit contains sealed maintenance-free batteries (VRLA).  When situated in 
a typical office environment, with the proper charging and limited cycling, these 
batteries can last many years. We recommend that the batteries be replaced 
every three years.

Never attempt to service batteries.  High voltage exists within the unit, which 
could cause electrical shock.  

Servicing of batteries should be performed or 

supervised by personnel knowledgeable of batteries and the required 
precautions

.  Keep unauthorized personnel away from batteries.  

When replacing the ED batteries, use the same number and type of batteries.

A. 

NEVER

dispose of batteries in a fire, as batteries will explode.

B. 

NEVER

dispose of used batteries or the UPS in the trash or landfill as it is 

against federal and state laws. 

The ED and Batteries must be recycled. 

For battery recycling information, please contact our service department for 
the name and address of the nearest battery recycling facility.

C. 

Spent batteries must be recycled in accordance with all Federal, State 

and local laws. To locate a recycling center near you contact the Falcon 
service department.

A. Do not open or mutilate the battery or batteries.  Released electrolyte is 

harmful to the skin and eyes.  It may be toxic.

B. A battery can present a risk of electrical shock and high short circuit current.  

REFER ALL BATTERY SERVICING OR REPLACEMENT TO A QUALIFIED 
SERVICE TECHNICIAN. UNTRAINED PERSONNEL SHOULD NEVER 

ATTEMPT BATTERY REPLACEMENT. 

WARNING

NEVER

CAUTION

10

Содержание ED3000-A

Страница 1: ... A FALCON ELECTRIC INC Irwindale CA 91706 Tel 626 962 7770 Fax 626 962 7720 The information contained herein is the property of FALCON ELECTRIC INC is proprietary confidential and not to be disclosed disseminated or used except for the purpose provided OMED3 4K LC 05 7 04 Rev A 5116 Azusa Canyon Road ...

Страница 2: ...t Panel LED Functions 5 Rear Panel Diagram Description 6 Chapter 4 Communications Interface 7 Signals Interfacing 7 Chapter 5 Operation 8 Step By Step Operating Procedure 8 Operational Mode Table 9 Chapter 6 Maintenance Technical Support 10 Care Maintenance 10 Battery Life vs Temperature 10 Battery Replacement 10 Storing the UPS and Batteries 11 FCC 11 Technical Support RMA Procedure 12 Requesting...

Страница 3: ...t to service batteries High voltage exists within the unit which could cause electrical shock Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions Keep unau thorized personnel away from batteries When replacing the optional ED batteries use the same number and type of batteries If configured with batteries allow at least 24 h...

Страница 4: ...y the input and output rating for your model INPUT OUTPUT SPECIFICATIONS The FALCON ED Series represents one of the smallest and most compact units of the FALCON Frequency Converter and Uninterruptible Power Supply UPS product line In the tradition of all FALCON products it maintains the highest reliability and the most complete on line sinewave power conversion and protection available An on line...

Страница 5: ...figured with a switching power supply is considered a non linear load which can be very abusive to most power conversion and protection equipment and could decrease its life expectancy The FALCON ED unit is specially designed to accept these loads and protect them efficiently with minimal of the output waveform degradation For ED models configured with batteries please refer again to the figure be...

Страница 6: ...ear enough to the computer or equipment to allow connection of the equipment power plugs to the receptacles located on the rear panel of the ED 4 DO NOT BLOCK UPS AIR VENTS THE UPS MUST NOT BE INSTALLED IN AN ENCLOSED AREA 5 Connect the equipment to be powered to the ED output receptacles located on the rear panel Verify that the connected equipment does not exceed the rated output in watts of the...

Страница 7: ...oaded call FALCON support for further assistance 4 LOW BATT LOW BATTERY WARNING INDICATOR The red LED will turn on when the ED is configured with an optional external battery bank operating in battery mode and the low battery level warning point has be reached Typically one minute of battery run time remains after the LED turns on 5 OVERLOAD FULL LOAD 75 LOAD 50 LOAD Adjacent to the red low batter...

Страница 8: ...RIS DO NOT OPERATE THE ED IN AN ENCLOSED SPACE 9 MAIN POWER SWITCH To turn on this unit toggle this switch to the on or 1 position To turn off this unit toggle this switch to the off or 0 position 10 INPUT FUSE Always replace this fuse with the same type and rating The fuse is a Bussman KTK R 30 30 Amp fuse 11 Battery Connector 72Vdc This connector may be connected to an optional external battery ...

Страница 9: ...CHAPTER 4 CHAPTER 4 DB 9 COMMUNICATIONS INTERFACE 7 ...

Страница 10: ... When power returns normal operation of the UPS resumes without any operator adjustment The duration of actual battery back up time and the low battery condition varies depending on the amount of load charge on the battery and condition of the battery Refer to the ED SPECIFICATIONS for approximate hold up times at 100 and 50 loads 9 Reset the input circuit breaker and turn the power switch OFF 10 ...

Страница 11: ... recommended that you leave the ED unit power switch ON at all times and switch your devices OFF individually This will ensure that your batteries are always at a maximum charged state The power switch acts as a system ON OFF switch When this switch is turned OFF power is lost to the entire unit including all outlets at the rear of the ED WARNING 9 ...

Страница 12: ...he unit which could cause electrical shock Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When replacing the ED batteries use the same number and type of batteries A NEVER dispose of batteries in a fire as batteries will explode B NEVER dispose of used batteries or the UPS...

Страница 13: ...rdance with the manufacturer s instructions may cause interference to radio and television reception All models covered in this manual have been tested and found to comply with the limits for a Class A computing device in accordance with the specifications in FCC regulations Part 15 Subpart J which are designed to provide reasonable protection against such interference If this equipment does cause...

Страница 14: ...ds The RMA number issued must appear on the outside of the shipping carton The original shipping container must be used when returning any ED Series product Falcon Electric will not assume any responsibility for shipping damage In the event of shipping damage you will be charged for repairs due to the damage All units must be returned prepaid The address and shipping instructions will be given to ...

Страница 15: ...ion Even with wide input variations in voltage and frequency the ED Series UVS Plus s output steadfastly remains at its designed voltage and frequency It also allows your system to continuously operate during extended brownouts to 88 VAC Enhanced Surge Start up Capability Falcon Electric s ED Series is designed to start loads that exhibit up to 1000 inrush current when started from utility This gi...

Страница 16: ...Load Change 1ms Recovery Time Output Protection Short Circuit and Overload Electrical Connections Input 6 Cord with 5 15P 8 Cord with 5 20P 8 Cord with L5 30P Hardwired Hardwired Output 4 5 15R 4 5 15R 4 5 15R Hardwired Hardwired Environmental Operating Temperature 0º C to 35º C 32º F to 95º F Humidity 10 to 95 Non Condensing Altitude 7 000 Feet Cooling Low Velocity Forced Air Fans Audible Noise 1...

Отзывы: