Fairford XFE Series Скачать руководство пользователя страница 8

8 M-85E0-F O81121

Overcurrent trip curve

0

.

1

1

10

100

1000

1

.

1

1

.

5

2

2

.

5

3

3

.

5

4

4.

5

5

5

.

5

6

C

l

a

ss

10B

C

l

a

ss

10

C

l

a

ss

20

C

l

a

ss

30

Tr

i

p L

e

v

el

Curr

e

n

t x I

n

S

ec

ond

s

t

o

T

r

i

p

'Current limit' and 'Overload level' settings are adjustable. The XFE monitors current in one phase only and this
limits overload currents in accordance with the trip curves shown here (See Menu structure for default settings).
Parameter P106 may be changed to select Class 10B, 10, 20 or 30. This will automatically change the motor
current rating (Trip level) of the unit to maintain over current protection.
Note: The  overload  monitors  one  of  the  phases  only  and  the  'Current  Limit'  level  is  only  active  during  motor
starting.

IMPORTANT

It is recommended that the control supply is maintained between starts to ensure the integrity of the overload,
which will reset on it's removal.

5

Product information

Cooling

The XFE is designed so that the rated start current/time is close to the maximum allowed. If the start duty is
exceeded the unit will trip. All XFE Soft Starts have a forced off cooling time between starts.
In line with the stated IEC starting duties, all XFE 100 series have an enforced off period of 2 minutes, likewise all
XFE 200 and XFE 300 series have an enforced off period of 7 minutes set as standard.  During this period the
display indicates 

“Stopped.Cooling”

, and the XFE will not respond to a start signal.

AC53a ratings are for Optimising or use without a bypass contactor.
AC53b rating is only for use with a bypass contactor and will trip if one is not used
Trip curves show the nominal times for operation from cold (40°C)

Содержание XFE Series

Страница 1: ...control supply before you apply the control supply voltage 115 230 select ISOLATION Caution The XFE uses semiconductor devices in the main circuit and is not designed to provide isolation For this re...

Страница 2: ...s Enclosure Ventilation When fitting the XFE into a cabinet ventilation must be provided if the heat output of the unit is greater than the cabinet will dissipate Use the following formula to determin...

Страница 3: ...Contactor Fig 2 4 Power circuit for In Delta connection of motors see note 4 Induction Motor U1 V1 V2 W2 W1 U2 In delta connections for correct rotation of motor Terml Fwd Rev T1 T2 T3 L1 L2 L3 W1 V1...

Страница 4: ...he selection of the correct XFE If the unit is supplied ready to set then it will force the selection of a starting Class when first powered up It is always possible to change the starting Class throu...

Страница 5: ...s menu The XFE will not start until the control display indicates Stopped and ready Applications Auto features Rated current P106 Start Class Current Optimise rate ENTER ENTER ENTER ENTER Starter Disa...

Страница 6: ...ss only Power Protection full optimise Current P27 Peak Start P40 supply volts 416 Real PF P22 Delay angle P23 Max angle P20 Reference PF P21 Internal PF Temperature I P Enter password Change password...

Страница 7: ...om line of display At any of the above stages pressing will return the user to the previous menu The XFE will now start and stop remotely from the START and STOP switches shown in Figure 2 1 but will...

Страница 8: ...s recommended that the control supply is maintained between starts to ensure the integrity of the overload which will reset on it s removal 5 Product information Cooling The XFE is designed so that th...

Страница 9: ...art of the ramp 9 Sensing Signal Short circuit thyristor or external noise during the ramp or during normal running 10 SCR Shorted Short circuit thyristor or motor side phase loss during the ramp 11 L...

Страница 10: ...1400 85 2068132 1400 1400 85 2 x 2067132 1000 2000 85 2 x 2067132 1250 2500 100 2 x 2067132 2000 4000 100 2 x 2067132 2000 4000 Short circuit Amp RMS kA SIBA Fuse Amps 2068132 1400 85 2068132 1250 42...

Страница 11: ...E 200 Series terminals XFE 300 Series terminals Normal service conditions Design standards and Approvals IEC 60947 4 2 EN 60947 4 2 AC Semiconductor Motor Controllers and Starters Ambient temperature...

Страница 12: ...A 1000A 842A 744A 1060A 1060A 904A 812A 1100A 1115A 940A 830A 1150A 1150A 980A 880A 1209A 1210A 1020A 900A 1150A 1150A 980A 880A 1209A 1210A 1020A 900A 1320A 1320A 1050A 930A 1360A 1360A 1080A 950A 14...

Отзывы: