7  M-85E0-F O81121

4

Set-up examples

1

Setting the XFE for large pump application

 

With

‘Starter Disabled’

 shown on the display, press

ENTER

 key once.

!

With

‘Applications’

 shown on the top line of the

display press 

ENTER

 once.

#

With

‘Settings’

 shown at the top of the display press

"

"

"

"

"

 key three times until 

‘Large pump’

 is shown at

top of display.

$

Press

ENTER

  once  to  select  large  pump.  The

display  will  indicate  the  parameters  changing  in
short intervals.

%

With the display top line indicating 

‘Send to store?’

,

press

ENTER

 to save the settings for a large pump

to permanent store. Display will flash the message

‘Storing’

 twice to indicate this has been done.

&

At any of the above stages pressing 

#

 will return the user to the previous menu. The XFE will not start until

the control display indicates 

‘Stopped and ready’.



‚

ƒ

„

…

Applications
Auto features

Settings
Default (keypad)

Send to store?
#=no Enter=yes

Large Pump
Conveyor

ENTER

#

#

#

ENTER

ENTER

ENTER

Starter Disabled
1:

q

to Enable

2

Setting the XFE for remote starting and stopping.

 

With

‘Starter Disabled’

 shown on the display,

press

ENTER

 key once.

!

With

‘Applications’

  shown  on  the  top  line  of

the  display  press 

"

"

"

"

"

key  twice  until 

‘Basic’

  is

shown at the top of the display.

#

Press

 ENTER

 once to select Basic menu.

$

Press

"

"

"

"

"

key twice until 

‘Starting’

 is shown at

top  of  the  display  then  press 

ENTER

  once  to

select starting option menu.

%

With display now indicating 

‘Starting’

 on top line

press

ENTER

 to toggle from 

‘Keypad Starting’

to

‘Remote Starting’

 as shown on bottom line

of display.

&

At any of the above stages pressing 

#

will return

the user to the previous menu.

The XFE will now start and stop remotely from the START and STOP switches shown in Figure 2.1, but will return to
keypad starting if the control supply on terminals X1 and X2 is removed.  Alternatively, to return to keypad starting and
stopping, repeat the above procedure and select 

‘Keypad Starting’

 at step 5.  

To keep the remote start/stop setting

after removal of the control supply, the settings must be permanently saved (See 3 below).



ƒ

„

…

‚

Applications
Auto features

ENTER

#

#

#

ENTER

ENTER

ENTER

†

Basic
Advanced

Starting
Keypad starting

Starting
Remote starting

ENTER

†

†

Disable starter
Enable starter
Starting

Starter Disabled
1:

q

to Enable

3

Permanently saving parameters set by user.

 

With

‘Starter Disabled

 shown on the display, press

ENTER

 key once.

!

With

‘Applications’

  shown  on  the  top  line  of  the

display press 

"

"

"

"

"

)

)

)

)

)

key four times until 

‘Permanent

Store’

 is shown at top of display.

#

Press

 ENTER

 once to select Permanent Store menu.

$

With

‘Save  Param’

  shown  at  top  of  display  press

ENTER

  once  to  permanently  save  parameters.

Display will flash twice to indicate this has been done.

%

At any of the above stages pressing 

#

 will return the

user to the previous menu.



ƒ

„

…

‚

Save parameter
Po

w

er on param

ENTER

†

#

#

ENTER

ENTER

Permanent store
Pass

w

ord

…

Applications
Auto features

Starter Disabled
1:

q

to Enable

The XFE should always be 

disabled

 before making changes. The Soft Starter then remains unable to drive the

load until it has been 

enabled

 via the 

Basic Menu

, or the control supply is removed and reapplied, or the 

 

 key

is pressed when prompted. If the Remote Start/stop is active the XFE cannot be 

enabled

.

Содержание XFE Series

Страница 1: ...control supply before you apply the control supply voltage 115 230 select ISOLATION Caution The XFE uses semiconductor devices in the main circuit and is not designed to provide isolation For this re...

Страница 2: ...s Enclosure Ventilation When fitting the XFE into a cabinet ventilation must be provided if the heat output of the unit is greater than the cabinet will dissipate Use the following formula to determin...

Страница 3: ...Contactor Fig 2 4 Power circuit for In Delta connection of motors see note 4 Induction Motor U1 V1 V2 W2 W1 U2 In delta connections for correct rotation of motor Terml Fwd Rev T1 T2 T3 L1 L2 L3 W1 V1...

Страница 4: ...he selection of the correct XFE If the unit is supplied ready to set then it will force the selection of a starting Class when first powered up It is always possible to change the starting Class throu...

Страница 5: ...s menu The XFE will not start until the control display indicates Stopped and ready Applications Auto features Rated current P106 Start Class Current Optimise rate ENTER ENTER ENTER ENTER Starter Disa...

Страница 6: ...ss only Power Protection full optimise Current P27 Peak Start P40 supply volts 416 Real PF P22 Delay angle P23 Max angle P20 Reference PF P21 Internal PF Temperature I P Enter password Change password...

Страница 7: ...om line of display At any of the above stages pressing will return the user to the previous menu The XFE will now start and stop remotely from the START and STOP switches shown in Figure 2 1 but will...

Страница 8: ...s recommended that the control supply is maintained between starts to ensure the integrity of the overload which will reset on it s removal 5 Product information Cooling The XFE is designed so that th...

Страница 9: ...art of the ramp 9 Sensing Signal Short circuit thyristor or external noise during the ramp or during normal running 10 SCR Shorted Short circuit thyristor or motor side phase loss during the ramp 11 L...

Страница 10: ...1400 85 2068132 1400 1400 85 2 x 2067132 1000 2000 85 2 x 2067132 1250 2500 100 2 x 2067132 2000 4000 100 2 x 2067132 2000 4000 Short circuit Amp RMS kA SIBA Fuse Amps 2068132 1400 85 2068132 1250 42...

Страница 11: ...E 200 Series terminals XFE 300 Series terminals Normal service conditions Design standards and Approvals IEC 60947 4 2 EN 60947 4 2 AC Semiconductor Motor Controllers and Starters Ambient temperature...

Страница 12: ...A 1000A 842A 744A 1060A 1060A 904A 812A 1100A 1115A 940A 830A 1150A 1150A 980A 880A 1209A 1210A 1020A 900A 1150A 1150A 980A 880A 1209A 1210A 1020A 900A 1320A 1320A 1050A 930A 1360A 1360A 1080A 950A 14...

Отзывы: