background image

Specifications (continued)

Performance Specifications 

Accuracy 
(ISA S51.1) 


0.25% Full Scale Guaranteed 
0.15% Full Scale Typical 

Hysteresis 
(ISA S51.1) 

0.1% Full Scale 

Deadband 

0.02% Full Scale 

(ISA S51.1) 

Repeatability 

0.1% Full Scale 

Position 
Effect 

No measurable effect 

Vibration 
Effect 

Less  than  1%  of  Span  under  the  following 
conditions:  5-15  Hz  @  0.8  inches  constant 
displacement 15-500 Hz @ 10 g's. 

R e v e r s e  
P o l a r i t y  
Protection 

No  damage  occurs  from  reversal  of  normal 
supply  current  (4-20  mA)  or  from  mis­
application of up to 60 mA. 

RFI/EMI 
Effect 

Less than 0.5% of span @ 30  /m class 3 Band 
ABC  (20  to  1000  mHz)  per  SAMA PMC  33.1 
1978 and less than 0.5% of span @ 10  /m level. 
2 Ghz band per EN 61000-4-3:1998+A1 EMC 
Directive  89/336/EEC  European  Norms  EN 
61326. 

v

S u p p l y  
Pressure 

Effect 

No measurable effect 

Effect 

Temperature 

[0.5% +0.04% / F  Temperature Change] of 
Span guaranteed 

+

 

-

psig 

[BAR] 

(kPa) 

psig 

[BAR] 

(kPa) 

psig 

[BAR] 

(kPa) 

Frequency 
Response 

3-15 

[0.2-1.0] 

(20-100) 

3-27 

[0.2-1.8] 

(20-180) 

6-30 

[0.4-2.0] 

(40-200) 

-3  db @ 5 Hz per  ISA  S26.4.3.1 

load configuration A. 

Materials  of 
Construction 

Chromate Treated 

Aluminum 

Nickel Plated Brass 

& Sapphire 

Stainless Steel 

Brass & Zinc Plated Steel 

Nitrile 

Epoxy Powder Coating 

Elastomers . . . . . . . . . . . . . . . . . . . . . .  
Finish . . . . . . . . . . . . .  

Body and Housing . . . . . . .  

Orifice . . . . . . . . . . . . . . .  

Trim . . . . . . . . . . . . . . . . . . . . .  

HAZARDOUS AREA CLASSIFICATION 

Factory Mutual (FM)  Approvals: 

Intrinsically Safe:  (4-20 mA only) 

(TDFI7800, TAFI7800) 

Class I, Division 1, Groups C and D;
Class II, Division 1, Groups E, F, and G;
Class III, Division 1,Fibers;
NEMA 4X Enclosure;
Temperature Code T4.

(TTFI7800, TRFI7800) 

Class I, Division 1, Groups C and D; 
Temperature Code T4. 

Non-Incendive:  (4-20 mA and voltage input units)

 (TDFI7800, TAFI7800, TDFN7800, TAFN7800) 

Class I, Division 2, Groups A, B, C and D;
Class II, Division 2, Groups F, and G;
Class III, Division 2;
NEMA 4X Enclosure;
Temperature Code T4.

(TTFI7800, TRFI7800, TTFN7800, TRFN7800) 

Class I, Division 2, Groups A, B, C and D;
Temperature Code T4.

Canadian Standards Association (CSA) Approvals: 

Intrinsically Safe:  (4-20 mA only)

      (TDCI7800, TACI780) 

Class I, Division 1, Groups C and D;
Class 11, Division 1, Groups E, F, and G;
Type 4 Enclosure;
Rated 4-20 mA, 30 VDC maximum;
Temperature Code T6.

(TTCI7800, TRCI7800) 

Class 1, Division 1, Groups C and D;
Temperature Code T6.

Approvals are valid when connected through a Shunt Zener 
Diode Safety Barrier that meets the parametric require­
ments shown in the following table. 

Parametric Requirements 

System

 Type 2: 

System

 Type 3: 

System

 Type 1: 

Dual Channel Polarized Rated: 28.5V  Max. 300 
Ohm Min. and 28V Diode return per channel. 

Dual Channel Polarized Rated: 28.5V  Max. 300 
Ohm Min. and 10V Max. 50 Ohm Min. 

Single Channel Polarized Rated: 28.5V  Max. 
300 Ohm Min. 

Division 2 Approvals:  (4-20 mA only)

 (TDCI7800, TTCI7800, TRCI7800)

Class I, Division 2, Groups A, B, C and D; 
Rated 4-20 mA, 30 VDC maximum; 
Temperature Code T6. 

(TACI7800) 

Class I, Division2, Groups A, B, C and D;
Class II, Division 2, Groups E, F, and G;
Type 4 Enclosure;
Rated 4-20 mA, 30 VDC maximum;
Temperature Code T6.

ATEX Approvals: 

Intrinsically Safe:  (4-20 mA only)

      (TAEI7800, TDEI7800, TTEI7800, TREI7800) 

EEx ia IIB, T4 (-20

0

 C to +72

0

 C) ambient

 II 1G (T4) 

      (TAEI7800, TDEI7800) 

IP65 Enclosure

Transducer Parameters 

Umax

 1 

Imax

 2 


28 V 
100 mA 

0.7 W 

Wmax

 3 

Ceq

 4 

Leq

 5 



Umax =  Maximum Voltage 

Imax = Maximum Current 

Wmax =  Maximum Power 

Ceq  =  Capacitance 

Leq  = Inductance 

Entity Parameters 

Vmax

 1 

30 VDC

Ci

 3 

Imax

 2 

200 mA

Li

 4 

0  mH 

Vmax =  Maximum Voltage 

Imax = Maximum Current 

Ci =  Capacitance 

Li = Inductance 

2

Содержание T7800 Series

Страница 1: ...DC input signal to a linearly proportional pneumatic output pressure SPECIFICATIONS Minimum Span 3 15 0 2 1 0 20 100 4 20 mA DC 0 10 VDC 1 9 VDC 0 5 VDC 1 5 VDC 20 120 1 5 8 0 150 800 5 0 35 35 3 27...

Страница 2: ...ltage input units TDFI7800 TAFI7800 TDFN7800 TAFN7800 Class I Division 2 Groups A B C and D Class II Division 2 Groups F and G Class III Division 2 NEMA 4X Enclosure Temperature Code T4 TTFI7800 TRFI7...

Страница 3: ...umalloy Inrare cases igntion sources due to impact and friction sparks couldoccur Thisshallbeconsideredwhentheequipment is installed in locations that specifically require Group II category1Gequipment...

Страница 4: ...Installation continued Figure 6 TR7800 Outline Dimensions Figure 5 TD7800 Outline Dimensions Figure 4 TT7800 Outline Dimensions 4...

Страница 5: ...Figure 8 Optional Mounting Kit 19254 1 sold separately Figure 7 Din Rail Mounting Kit 16893 1 included with unit 5...

Страница 6: ...tream to avoid interference with transducer performance The user is responsible for ensuring that the environmentinwhichtheunit isinstalledand the operating gas are compatible with the materials in th...

Страница 7: ...desiredoutputrangeis obtained SPLIT RANGEOPERATION Lo Hi Span Adjustment 1 Set the Lo Hi Span switch to the Lo position for 3 9 psig or 9 15 psig output range and for 4 20 mA input range Set the Lo Hi...

Страница 8: ...Calibrations Adjustments continued Figure 10 T7800CalibrationConfiguration 8...

Страница 9: ...11 1 12 1 13 14 15 16 17 1 18 19 Qty Cover Machining Screw Screw Gasket Nozzle Body Assembly Orifice Assembly Spring Disk Diaphragm Spacer Ring Diaphragm Assembly Foam Block Valve Body Assembly Screw...

Страница 10: ...n with alcohol and dry with compressed air NOTES 1 Parts must be completely dry before reassembling 2 If the standard maintenance procedure does not correct the problem install the appropriate service...

Отзывы: