MAINTENANCE
TROUBLESHOOTING
Table 6.
Troubleshooting
Problem
Solution
(check)
No output
• Supply pressure
• Clogged orifice
Leakage
• Connections
Low or improper
Span adjust
• Zero and Span adjust
• Low supply pressure
• Output leakage
Erratic operation
• DC signal
• Loose wires or connections
• Liquid in air supply
To clean the Orifice, use the following procedure:
1.
Shut off the valve that supplies air to transducer.
It is
not necessary to remove the Transducer from the
air line.
2.
Remove the Orifice Assembly (
6
) from the unit. For
more information, see Figure 11.
3.
Clean with alcohol and dry with compressed air.
NOTES: 1. Parts must be completely dry before
reassembling.
2. If the standard maintenance procedure
does not correct the problem, install the
appropriate service kit.
WARNING: Transducer failure could result in output
pressure increasing to supply pressure
and possibly causing personal injury or
damage to equipment.