background image

Pneumatic Connection 

Clean all pipelines to remove dirt and scale before installation. Apply 
a minimum amount of pipe compound to the male threads of the 
fitting only.  

Do Not use teflon tape as a sealant. 

 Start with the third 

thread back and work away from the end of the fitting to avoid 
contaminating the transducer.  Install the transducer in the air line. 
The inlet and outlet ports are labeled on the ends of the transducer. 
Tighten connections securely.  Avoid undersized fittings that will limit 
the flow through the transducer and cause pressure drop down 
stream. 

NOTE: 

Oil free air  is required.  Use a filter to remove dirt and 
liquid in the air line ahead of the transducer.  If an air 
line lubricator is used, it MUST be located down­
stream to avoid interference with transducer perfor­
mance. 

The user is responsible for insuring that the environ­
ment in which the unit  will be installed and the 
operating gas are compatible with the materials in the 
transducer. 

Electric Connection 

Make connections as shown in Figure 8. 

CAUTION: 

Effective November 1997 (DATE CODE NE),  the DIN 

Connector terminal connections have been changed.  The ground 
connection has been moved from terminal  #3 to the (   ) terminal. 
When replacing an existing unit, correct wiring on the mating 
connector. 

Wiring in Hazardous Areas 

Table 1.  

Hazardous Location Wiring Practices. 

Country 

Agency 

Code 

U.S. 
Canada 
Europe 

FM 
CSA 
ATEX 

ANSI/ISA RP 12.6 & ANSI/NFPA 70 
CEC Part 1 

EN 50 039, EN 60079-14, IEC 60079-14 

Intrinsically Safe Connections

Table 2.  

Intrinsically Safe Installation Drawings. 

Underwriting Group 

Drawing Number 

FM (Factory Mutual) 
CSA (Canadian Standards) 
ATEX 

EC-16984 
EC-18005 
EC-18007 

Limitations/Exceptions

Type 3R - TAF, TDF upright position 

TFA - CL I, Div 2 wiring per NEC ANSI/NPFA 70 for installation 
without wiring parameters. TDF, TTF, TRF require an enclosure. 

For dry locations and voltages less than 60Vdc, TTF & TRF 
units must be in an enclosure. 

Where loop voltages exceed 60Vdc (dry locations) or 30Vdc 
(potentially damp locations), the TTF and TRF versions 
must be installed meeting the electrical shock and fire 
protection requirements of ANSI/ISA S82.01. 

MAINTENANCE 

To clean the Orifice, use the following procedure: 
1. 

Shut off the valve that is supplying air to transducer. 

It is not necessary to remove the Transducer from 
the air line. 

2. 

Remove the Orifice Assembly from the unit.  For 
detailed information see Figure 1  “T6000 Calibration 
Configuration on page 1. 

3. 

Clean with alcohol and dry with compressed air. 

NOTES: 

Parts must be completely dry before reassembling. 

If the standard maintenance procedure does not 
correct the trouble, install the appropriate Service 
Kit below: 
16798-1 

  (3-15, 3-27 & 6-30 psig

 Standard Range)

18238-1 

(0-30 psig Extended Range)

18239-1 

(0-60 psig Extended Range)

18240-1

 (0-120 psig Extended Range)

18039-1 

(Explosion-Proof Base)

Service Kits also include Gasket, O-Rings, and 
Membranes to replace "W" Option product. 

TROUBLE-SHOOTING 

Table 1.  

Trouble-Shooting. 

Problem 

Solution 

(check) 

No Output 

Supply Pressure 
Clogged Orifice 
Input Signal 

Leakage 

Pneumatic Connections 

Low or Improper 
Span Adjust 

Zero and Span Adjust 
Supply Pressure Low 
Output Leakage 

Erratic Operation 

DC Signal 
Loose Wires or Connections 
Liquid in Air Supply 
Dirt in Magnet Gap 

WARNING: Failure of Transducer could result in out­

put pressure increasing to supply pres­
sure possibly causing personal injury or 
damage to equipment. 

3

Отзывы: