Page 17/37
SEPARIX-C/-T and SEPARIX-Control CT
4.4
Faults and alarms
In case of a fault or an alarm the factory-set SEPARIX-Control CT triggers with the buzzer
an audible alarm signal. In case of a fault, additionally the yellow fault LED blinks, and with
an alarm, additionally the red alarm LED blinks.
4.4.1
Overview of fault and alarm causes
Figure
7
:
SEPARIX-Control CT, fault and alarm display
Blink code
Power LED (green)
Fault LED (yellow)
Alarm LED (red)
1x short
Interface sensor
Interface sensor
Oil layer
2x short
High-level sensor
High-level sensor
High level
3x short
Interface sensor and
high-level sensor
Interface sensor and
high-level sensor
Oil layer
and high level
4.4.2
Acknowledgement of faults or alarms
•
Press red acknowledge button.
The fault or alarm is acknowledged and the buzzer stops. The yellow or red LED
continues to blink because the cause of the fault or alarm has not yet been cor-
rected.
Faults and alarms are repeated every 24 hours after they have been
acknowledged (red acknowledge button pressed) so that they are
brought to the system operator's attention again.
1: Power LED (green)
2: Fault LED (yellow)
3: Alarm LED (red)
4: Acknowledge button (red)
5: Test button (yellow)
Содержание SEPARIX-C L Plus
Страница 25: ......
Страница 26: ......
Страница 29: ......
Страница 30: ......
Страница 31: ......
Страница 32: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 41: ...Blank Page...
Страница 42: ...Blank Page...
Страница 43: ...Blank Page...