Electrical connection
The following table shows the maximum total resistances at different supply voltages, and
cable resistances at various cross-sections:
Supply volt-
age [V]
Max. total re-
sistance
[Ω]
Cable cross-
section
[mm²]
Cable resistance
per m copper ca-
ble
[Ω/
m]
For connection
housing HPH Ex d
suitable (yes/no)
12 (-5%)
158
0.5
0.0356
no
1.0
0.0178
no
1.5
0.0119
no
24 (-5%)
688
0.5
0.0356
yes
1.0
0.0178
yes
1.5
0.0119
yes
The max. cable length is calculated as follows:
L = (((U – U
min
) / I
max
) – R
B
) / R
Q
L
= Cable length [m]
U = Supply voltage [V] (with negative tolerance value -5%)
U
min
= Minimum supply voltage [V] = 8 V
I
max
= Maximum power consumption [A] = 0.0215 A
R
B
= Load
R
Q
= Cable resistance per m copper cable [
Ω
/m] at cable cross-section Q [mm²]
Example:
Supply voltage: 12 V (± 5%)
Supply voltage U = 11.4 V (12 V - 5%)
Minimum supply voltage U
min
= 8 V
Maximum power consumption I
max
= 0.0215 A
Load R
B
= 86.8
Ω
Cable resistance per m copper cable R
Q
= 0.0356
Ω
/m at cable cross-section Q = 0.5 mm²
L = (((11,4 – 8) / 0,0215) - 86,8) / 0,0356 = 2000 m
Thus a cable with forward and return line (2-wire) can be up to 1000 m long.
Содержание HART TORRIX
Страница 24: ......
Страница 25: ......
Страница 26: ......
Страница 27: ......
Страница 28: ......
Страница 29: ......
Страница 30: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 41: ...Blank Page ...
Страница 42: ...Blank Page ...
Страница 43: ...Blank Page ...