INSTALLATION AND WIRING
2.21
Temperature Calibration Adjustment (V5022)
Temperature Calibration Adjustment is a ± 3276.7
E
C or
E
F value which is added to the controller
measured Process Temperature. This location can be used to remove inaccuracies due to thermocouple
cold junction compensation errors (see page 2.7) and temperature input device errors (typical
thermocouple device inaccuracy is ±1 to ±3
E
C). If no adjustment is required then this location should
be set equal to zero.
Process Temp. (V5005) = Actual Temp. (measured) + Cal. Adjustment (V5022)
Examples:
Actual Temperature = 24.6
E
C
Process Temperature = 25.2
E
C
Temperature Calibration Adjustment = 32768+6 = 32774 = -.6
E
C
Actual Temperature = 28.2
E
C
Process Temperature = 26.3
E
C
Temperature Calibration Adjustment = 19 = +1.9
E
C
TEMPERATURE CONTROLLER MEMORY MAP, 4 LOOPS
The following example V-Memory map shows the addressing for all four loops of a Temperature
Controller Module with a Table Beginning Address of V5000. Any V-Memory address maybe specified
as the loop table starting address for a given module. Normally retentive V-Memory is used to store loop
parameters (V2000-V7377).
LOOP 1
LOOP 2
LOOP 3
LOOP 4
DESCRIPTION
5000
5001
5002
5003
5004
5005
5006
5007
5010
5011
5012
5013
5014
5015
5016
5017
5020
5021
5022
5023
5024
5025
5026
5027
5030
5031
5032
5033
5034
5035
5036
5037
5040
5041
5042
5043
5044
5045
5046
5047
5050
5051
5052
5053
5054
5055
5056
5057
5060
5061
5062
5063
5064
5065
5066
5067
5070
5071
5072
5073
5074
5075
5076
5077
5100
5101
5102
5103
5104
5105
5106
5107
5110
5111
5112
5113
5114
5115
5116
5117
5120
5121
5122
5123
5124
5125
5126
5127
5130
5131
5132
5133
5134
5135
5136
5137
Mode Word
SetPoint
Bias
Output
Alarm Word
Temperature
Gain
Reset
Rate
Low Alarm
High Alarm
Deviation Alarm
Alarm Deadband
SP Low Limit
SP High Limit
Input type
Control Period
Hysteresis
Calibration Adj
Spare
Spare
Spare
Spare
Spare
Содержание Direct Logic 405
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 16: ...INTRODUCTION 1 6...
Страница 38: ...INSTALLATION AND WIRING 2 22...
Страница 45: ...SUPPORTING LADDER LOGIC 3 7...
Страница 47: ...SUPPORTING LADDER LOGIC 3 9...
Страница 48: ...SUPPORTING LADDER LOGIC 3 10...
Страница 62: ...TROUBLESHOOTING 6 4...