INSTALLATION AND WIRING
2.11
TEMPERATURE CONTROLLER LOOP CONFIGURATION MEMORY
All V-Memory values are in hexadecimal. Use the DirectSoft BCD/Hex or Binary data type to monitor
loop bit mapped values, use decimal data type to display or monitor all other loop V-Memory values.
NOTE:
The
Direct
Soft
decimal data type will convert a hexadecimal value, 0-0FFFFH, to it's decimal
equivalent, 0-65535. It will not display negative numbers with a minus sign. Hegative numbers
will appear as values greter than 32768. For example, -0.1 = 32768 (08001H) and -
3276.7=65535 (0FFFFH).
The values in parenthesis in the following table show the allowable range for that V-Memory location.
The values are shown after the hexadecimal to integer conversion and include the location of the implied
decimal point.
Temperature values range from -3276.7 to +3276.7. If a temperature is negative the most significant bit
in the V-Memory location is set. Temperature values are selectable for units of either degrees C or
degrees F.