![FACTS Engineering Direct Logic 405 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/facts-engineering/direct-logic-405/direct-logic-405_manual_3159079026.webp)
INSTALLATION AND WIRING
2.10
Error Flag
The dedicated V-Memory Error location for each Controller is used to report configuration and diagnostic
errors. This location is bit mapped. If any one of the fatal errors is detected at power up, the TB and
24V LEDs will flash back and forth until the error is cleared.
Hexadecimal Weight
Bit Number
Bit Description
Fatal Errors
0001
0
Undefined
0002
1
On if Starting table address below user v-memory
0004
2
On if Starting table address too high
0008
3
On if More than 4 loops enabled
0010
4
On if Starting address is too high for number of loops
0020
5
On if Dedicated V-Memory Configuration Error
0040
6
On if Temperature Controller Configuration Error
0080
7
On if ROM Error, Incorrect Checksum
Warning Errors
0100
8
Undefined
0200
9
Undefined
0400
10
Undefined
0800
11
Undefined
1000
12
Undefined
2000
13
Undefined
4000
14
Undefined
8000
15
On if the LTC CPU has gone through a Watch-Dog
Time-Out
Example:
If Error Flag contains 0004 then the starting table address is too high.
Version
The dedicated V-Memory Version location for each Controller holds the Controller's firmware Version
number. The firmware version is written to this location after a reset.
Example
A firmware version 1.01 Controller in slot 4 will return 0101 in V7734.
Содержание Direct Logic 405
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 16: ...INTRODUCTION 1 6...
Страница 38: ...INSTALLATION AND WIRING 2 22...
Страница 45: ...SUPPORTING LADDER LOGIC 3 7...
Страница 47: ...SUPPORTING LADDER LOGIC 3 9...
Страница 48: ...SUPPORTING LADDER LOGIC 3 10...
Страница 62: ...TROUBLESHOOTING 6 4...