Installatie handleiding

 

 

9 < 

<

 

<

 

<

 

 

C

11

, Wall terminal. 

3.6.1

For a facade or wall outlet use a wall terminal. 
(fig.4.1 C

11

Depending on the calculation this can be a 
diameter of 130/200mm or 100/150mm.

 

 

C

31

, Roof terminal. 

3.6.2

For a flat or pitched roof outlet use a long roof 
outlet with a diameter of 100/150mm (fig.4.1 C

31

 

C

91

, Existing chimney. 

3.6.3

For an existing chimney use the short chimney 
outlet with a diameter of 100/150mm (fig.4.1C

91

). 

 
In this case the existing chimney acts as air inlet an 
inserted flexible stainless steel pipe discharges the 
flue gases. The top and the bottom should be 
airtight. 
Depending on the calculated outlet diameter, use a 
flexible stainless steel tube of Ø 100mm or Ø 
130mm with CE marking for 600°C. 

 

Please note: 

The minimum chimney diameter for a 130mm 
flexible stainless steel pipe must 200 x 200mm. 
And for a 100mm flexible stainless steel pipe 
150x150mm.  

 

Preparation and installation 

4

instructions 

 

Gas connection 

4.1

See also chapter 3  Installation requirements. 
 

Calculate/Size the pipe so that no pressure drop 
occur in the gas pipe. 

 

Please note  

Provide a flexible gas connection with at least ½ 
meter extra length to allow for installation and 
service of the control unit (fig. 1.7) 

 

Preparing the fire 

4.2

Remove the fire from its packaging! 

 

Please note:

 

Ensure that

 

the gas supply pipes under the 

appliance are not damaged.  
Remove frame and glass and take the packaged 
parts from the fire. 
Store the frame and glass in a safe place. 
Prepare the gas connection on the gas valve 
 
 
 

 

Positioning of the fire  

4.3

Take the installation requirements into account see 
Chapter 3.  
 

Place the unit in the desired position and set the 
height and level of the fire with the adjustable legs 
supplied (Fig. 1.2c). 
Rough height adjustment can be achieved with the 
extendable leg or with the long legs supplied.  
Fine adjustment can be achieved with the 
adjustable feet.. 

 

 Suspended from the wall 

4.3.1

The appliance can be mounted suspended from 
the wall with the use of the suspension bracket 
(Fig.1.3).   

 

Installing the flue materials  

4.4

 

When penetrating a wall or ceiling the opening 
must be at least 5mm larger than the diameter 
of the flue pipe. 

 

Horizontal sections should be installed with a 
slope of 3 degrees towards the fire. 

 

Build the system from the fire. If this is not 
possible you can make use of an extendable 
adapter section. 

 

Where an adjustable section cannot be used, a 
1/2 meter cut down pipe, which can be 
shortened as required, can be used instead. 
When shortening this type of pipe, ensure that 
the inner pipe is 2cm longer than the outer 
pipe. 

 

Pipes that have been shortened must be 
secured to the next pipe with self-tapping 
screws. 

 

The tail end of wall and roof terminals can also 
be shortened as required, leaving a minimum 
of 150mm of twin-wall pipe, i.e. the 150mm 
measurement does not include the outdoor 
part of the terminal. 

 

When enclosing flue material within any sort 
of structure, the pipes must not be insulated 
but ventilated instead (approx. 100cm2). 

 

Constructing the false chimney 

4.5

If possible, carry out a performance test on the fire 
before finally finishing the installation. 
Chapter 7 “checking the technical parts of  
installation” 

Содержание Triple Premium XXL

Страница 1: ...Triple Premium XXL 40011590 1529 Triple Premium XXL ENG ...

Страница 2: ...Installatie handleiding 2 1 1 1 2 1 3 1 4 1 5 1 6 C ...

Страница 3: ...Installatie handleiding 3 1 7 1 8 1 9 2 1 a 2 1 b 2 1 c 2 1 d C ...

Страница 4: ...Installatie handleiding 4 2 2 2 3 2 4 2 5 2 7 2 8 2 9 H F F X C X T S A ...

Страница 5: ...Installatie handleiding 5 3 1 3 1 a 3 1 b 3 1 c ...

Страница 6: ...Installatie handleiding 6 4 1 4 2 5 1 a 5 1 b 5 1 c 5 1 d 5 1 e ...

Страница 7: ...t materials than specified Safety instructions 2 The unit must be installed and subsequently serviced every year and maintained in accordance with these instructions and the applicable national and local regulations Ensure that the data on the type label matches the local gas type and pressure The settings and the construction of the fire must not be changed The 230V electric cable may be only rep...

Страница 8: ...s connection pipe with at least meter extra length to allow for installation and service of the control unit fig 1 7 False chimney breast or other 3 4 structure The False chimney should be made entirely of non combustible material The space above the fire should always be ventilated using grids with minimal free passage of 200cm per grid Never build directly onto the built in frame of the applianc...

Страница 9: ...nection on the gas valve Positioning of the fire 4 3 Take the installation requirements into account see Chapter 3 Place the unit in the desired position and set the height and level of the fire with the adjustable legs supplied Fig 1 2c Rough height adjustment can be achieved with the extendable leg or with the long legs supplied Fine adjustment can be achieved with the adjustable feet Suspended ...

Страница 10: ...S T and Q covers fig 2 7 to 2 9 C spacer fig 2 2 B and C F fig 2 3 D fig 2 2 H fig 2 5 Please note Ensure that the fire is not load bearing with regard to the false chimney breast or other structural elements Pay special attention to the following points 1 Check during work that the glass can be inserted and removed easily 2 Check during work that the covers T fig 2 7 and 2 8 or Q fig 2 9 fit corr...

Страница 11: ... the chips on the burner and on the cover plate Prevent a thick layer on the burner this adversely affects the flame pattern Glow wire 6 1 1 The glow wire gives a decorative glow effect Pull the wire well apart and place tufts in different places on the burner Please note Do not use the glow wire near the ignition and ionisation plugs as this can cause a short circuit in the ignition system Pebble...

Страница 12: ...and connect a pressure gauge hose to the test point Connect your meter on the measure point B see fig 1 7 Open the gas tap isolator The pressure must match the value specified in the technical data of this manual When the inlet pressure is 5mb higher or lower do not connect the appliance and get in contact with the gas supply company How to check burner pressure This test can only be performed if ...

Страница 13: ... with your fire is to use the free Faber Flue App which can be download from INTERNET BlackBerry Android PC with Google Chrome browser APP store iPhone iPad and Mac Google Play Android smartphones and Android tablets Alternatively use the flue calculation table see tables below and sections 12 and 13 The alternatives of outlet lengths and any restrictors are set out in the restrictor table In the ...

Страница 14: ...x 30 or 45 bends in the vertical part Table Select from the table the correct vertical TVH and horizontal length THL If the result is x or if the values are outside the table then the combination is not allowed The TVH or THL can be adjusted to achieve a viable system If a value is indicated check that the calculated STL value is not lower than indicated in the table In this case STL must be adjus...

Страница 15: ...x x x x x x x x x x 9 0 2 x x x x x x x x x x 10 0 2 x x x x x x x x x x 11 30 2 x x x x x x x x x x 12 30 2 x x x x x x x x x x 13 30 2 x x x x x x x x x x 14 30 2 x x x x x x x x x x 15 30 2 x x x x x x x x x x 16 40 2 x x x x x x x x x x 17 40 2 x x x x x x x x x x 18 40 2 x x x x x x x x x x 19 40 2 x x x x x x x x x x 20 40 2 x x x x x x x x x x 21 50 2 x x x x x x x x x x 22 50 2 x x x x x x...

Страница 16: ...0 4 60 4 60 4 50 4 50 4 x x x x 11 70 4 70 4 70 4 60 4 60 4 60 4 50 4 x x x x 12 70 4 70 4 70 4 70 4 60 4 60 4 60 4 x x x x 13 80 4 80 4 70 4 70 4 70 4 60 4 60 4 x x x x 14 80 4 80 4 80 4 70 4 70 4 70 4 60 4 x x x x 15 80 4 80 4 80 4 80 4 70 4 70 4 70 4 x x x x 16 80 4 80 4 80 4 80 4 80 4 70 4 70 4 x x x x 17 80 4 80 4 80 4 80 4 80 4 80 4 70 4 x x x x 18 80 4 80 4 80 4 80 4 80 4 80 4 80 4 x x x x ...

Страница 17: ...Installatie handleiding 17 Example 12 fig 12 1 fig 1 2 2 fig 12 3 ...

Страница 18: ...k component that is placed on the fire value completed Flue length from 0 1 0 45 m 0 2 Flue length from 0 5 0 90 m 0 5 Flue length from 1 0 1 40 m 1 Flue length from 1 5 2 00 m 1 5 Flue length from 2 00 m und mehr 2 Bends 90 0 1 Bends 45 oder 30 0 2 Roof terminal 1 Wall terminal 0 Total ...

Страница 19: ...e horizontal flue length x 1 5 45 bends in the horizontal flue length x 1 90 bends from Vertical to horizontal Vice versa x 0 4 45 bends from Vertical to horizontal Vice versa x 0 2 Pipes running upwards at an angle In meters x 0 7 total _______ Meter Search in the table at TVH and THL and enter the value that is found Found value If the detected value is a number check whether the completed STL i...

Страница 20: ...mm Ectra information found value behind the comma Mark which is applied Install the air reducer plate See the installation manual 0 1 Install the adapter 200 130 to 150 100mm direct on top of the fire 0 2 In case of wall terminal Install the adapter 200 130 to 150 100mm before the last bend In case of roof terminal Install the adapter 200 130 to 150 100mm before the terminal 0 3 In case of roof te...

Страница 21: ... mbar 20 30 37 Gas rate at 15ºC and 1013 mbar M3h 1 511 0 461 0 588 Gas rate at 15ºC and 1013 mbar gr h 1180 1100 Burner pressure at full mark mbar 11 5 24 33 5 Burner pressure low mark mbar 4 6 6 Injector main burner mm 660 660 220 230 220 230 Diameter inlet outlet mm 200 130 200 130 200 130 Gas control valve SIT 845 SIT 845 Sit 845 Gas connection Electrical connection V 220 220 220 Batteries sen...

Страница 22: ...UK indication Position Distance in mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each othe...

Страница 23: ...Installatie handleiding 23 Drawings 16 Triple Premium XXL 16 1 ...

Страница 24: ...Installatie handleiding 24 Builder s opening and control box dimensions 16 2 ...

Страница 25: ...Installatie handleiding 25 Builder s opening and ventilation grills dimensions 16 3 ...

Страница 26: ......

Отзывы: