Installatie handleiding
9 <
<
<
<
C
11
, Wall terminal.
3.6.1
For a facade or wall outlet use a wall terminal.
(fig.4.1 C
11
)
Depending on the calculation this can be a
diameter of 130/200mm or 100/150mm.
C
31
, Roof terminal.
3.6.2
For a flat or pitched roof outlet use a long roof
outlet with a diameter of 100/150mm (fig.4.1 C
31
)
C
91
, Existing chimney.
3.6.3
For an existing chimney use the short chimney
outlet with a diameter of 100/150mm (fig.4.1C
91
).
In this case the existing chimney acts as air inlet an
inserted flexible stainless steel pipe discharges the
flue gases. The top and the bottom should be
airtight.
Depending on the calculated outlet diameter, use a
flexible stainless steel tube of Ø 100mm or Ø
130mm with CE marking for 600°C.
Please note:
The minimum chimney diameter for a 130mm
flexible stainless steel pipe must 200 x 200mm.
And for a 100mm flexible stainless steel pipe
150x150mm.
Preparation and installation
4
instructions
Gas connection
4.1
See also chapter 3 Installation requirements.
Calculate/Size the pipe so that no pressure drop
occur in the gas pipe.
Please note
Provide a flexible gas connection with at least ½
meter extra length to allow for installation and
service of the control unit (fig. 1.7)
Preparing the fire
4.2
Remove the fire from its packaging!
Please note:
Ensure that
the gas supply pipes under the
appliance are not damaged.
Remove frame and glass and take the packaged
parts from the fire.
Store the frame and glass in a safe place.
Prepare the gas connection on the gas valve
Positioning of the fire
4.3
Take the installation requirements into account see
Chapter 3.
Place the unit in the desired position and set the
height and level of the fire with the adjustable legs
supplied (Fig. 1.2c).
Rough height adjustment can be achieved with the
extendable leg or with the long legs supplied.
Fine adjustment can be achieved with the
adjustable feet..
Suspended from the wall
4.3.1
The appliance can be mounted suspended from
the wall with the use of the suspension bracket
(Fig.1.3).
Installing the flue materials
4.4
When penetrating a wall or ceiling the opening
must be at least 5mm larger than the diameter
of the flue pipe.
Horizontal sections should be installed with a
slope of 3 degrees towards the fire.
Build the system from the fire. If this is not
possible you can make use of an extendable
adapter section.
Where an adjustable section cannot be used, a
1/2 meter cut down pipe, which can be
shortened as required, can be used instead.
When shortening this type of pipe, ensure that
the inner pipe is 2cm longer than the outer
pipe.
Pipes that have been shortened must be
secured to the next pipe with self-tapping
screws.
The tail end of wall and roof terminals can also
be shortened as required, leaving a minimum
of 150mm of twin-wall pipe, i.e. the 150mm
measurement does not include the outdoor
part of the terminal.
When enclosing flue material within any sort
of structure, the pipes must not be insulated
but ventilated instead (approx. 100cm2).
Constructing the false chimney
4.5
If possible, carry out a performance test on the fire
before finally finishing the installation.
Chapter 7 “checking the technical parts of
installation”
Содержание Triple Premium XXL
Страница 1: ...Triple Premium XXL 40011590 1529 Triple Premium XXL ENG ...
Страница 2: ...Installatie handleiding 2 1 1 1 2 1 3 1 4 1 5 1 6 C ...
Страница 3: ...Installatie handleiding 3 1 7 1 8 1 9 2 1 a 2 1 b 2 1 c 2 1 d C ...
Страница 4: ...Installatie handleiding 4 2 2 2 3 2 4 2 5 2 7 2 8 2 9 H F F X C X T S A ...
Страница 5: ...Installatie handleiding 5 3 1 3 1 a 3 1 b 3 1 c ...
Страница 6: ...Installatie handleiding 6 4 1 4 2 5 1 a 5 1 b 5 1 c 5 1 d 5 1 e ...
Страница 17: ...Installatie handleiding 17 Example 12 fig 12 1 fig 1 2 2 fig 12 3 ...
Страница 23: ...Installatie handleiding 23 Drawings 16 Triple Premium XXL 16 1 ...
Страница 24: ...Installatie handleiding 24 Builder s opening and control box dimensions 16 2 ...
Страница 25: ...Installatie handleiding 25 Builder s opening and ventilation grills dimensions 16 3 ...
Страница 26: ......