b.

c.

If specific interference sources cannot be avoided, they should at least 
be kept at a distance from the regulator system.

Capacitive and inductive couplings can cause crosstalk between high-
voltage lines and parallel low-voltage and sensor lines. This distorts 
measured values and signals and can disrupt the entire regulatory 
process. It is therefore recommended that all sensors and signal lines be 
placed separately from the control and mains voltage lines.

If possible, a separate mains line should be provided to feed the regula-
tor system. This helps reduce any interference penetrating the regulator 
via the mains supply line. Voltage surges resulting from switching 
substantial loads will also then be less of a problem.

In the case of contactors, solenoid valves and other inductive consu-
mers, the induction voltage occurring during switching has to be redu-
ced by appropriate protection methods. The choice of methods depends 
on whether the consumer runs on DC or AC voltage.

!

DC voltage

In the case of d/c voltage systems, the induction voltage occurring 
can, for example, be limited by using self-induction diodes, 
varistors or suppresser diodes. The diagram on the left shows one 
possibility using a self-induction diode.

!

AC voltage

In the case of a/c voltage, interference suppression as described 
above is not possible. Instead, an RC combination must be used. 
An RC filter must be connected as directly as possible to the 
inductance, in order to ensure a short line. In addition, the 
component ratings of the RC combination must be geared to the 
inductance. Too low ratings lead to excessive voltage, and too high 
ratings cause significant losses in the interference suppresser 
component. Another point to note here is that only capacitors which 
meet VDE 0656 may be used. They must be suited to the mains 
voltage and designed for very high switching voltages. The diagram 
on the left shows inductance interference suppression using an RC 
filter.

An RC filter should not be fitted directly to the regulator's switching 
contact, as shown on the left, as an idle current will flow through the RC 
combination even when the switching contact is open. This current may 
be enough to mean that a downstream contactor is not de-energised 
and a closed protective contact does not reopen.

d.

e.

Diode

Coil

Regulator contact

U +

U -

RC-
Filter

Coil

Regulator contact

AC

Содержание Dari-Kool 720012

Страница 1: ...2016 Installation and Operation Manual Control for milk cooling tanks COMPACT KOOL...

Страница 2: ...ion Page 9 Programming level operation Page 10 Configuration level operation Page 11 Intermediate stirring options during cooling Page 13 Continuous stirring in OFF mode Page 13 Setting the actual val...

Страница 3: ...pressing a button Cooling mode Press the 4 8 button the compressor and agitator operate automati cally In between cooling periods agitator and compressor LEDs off intermediate stirring can be activat...

Страница 4: ...ce must not be installed in potentially explosive atmospheres The control cabinet for milk cooling tanks fulfils the EC requirements for electromagnetic compatibility EMC and the Low Voltage Directive...

Страница 5: ...it is necessary to shorten or lengthen the sensor cable on installation or if a sensor other than the one supplied is to be fitted the actual value correction parameter must be adjusted accordingly S...

Страница 6: ...itching contactor and motor protection switch 2 make contacts 16A AC 1 250 V 13 mm LED Display 3 digits 0 1 C 1 0 C two step controller 50 150 C 0 1 to 99 9 K free adjustable standard adjusting 0 7 K...

Страница 7: ...of the regulator are set As subsequent interventions by the end user after the parameters have been set can result in dangerous chan ges to functions which might not be immediately obvious access to t...

Страница 8: ...kly Release button SET To store the changed parameter in the memory first release the arrow button and then button SET Switching back to working level possible from any parameter Press button Arrow UP...

Страница 9: ...ds or downwards Button Agitator in cooling mode press for appr 1 sec SHORT intermediate stirring press for appr 3 sec LONG intermediate stirringSee also the section describing the intermediate stirrin...

Страница 10: ...n after being turned off Parameter C50 Duration of SHORT intermittent stirring Duration min of stirring after short pressing of the intermittent stirring button Parameter C51 Duration of LONG intermit...

Страница 11: ...he hysteresis is always upwards In the case of heating contacts it is below the target temperature cooling or heating contact is set at configuration level In the symmetrical hysteresis mode the value...

Страница 12: ...g of minimum pause time for compressor relay contacts K1 in order to prevent repeated switching on and off Range 0 0 999 seconds Parameter P80 Switch from target temperatur T1 to T2 Setting of funktio...

Страница 13: ...diately otherwise Intermediate stirring LONG will be activated Intermediate stirring LONG Press agitator button for approx 3 secs until Lon appears in the display The duration of SHORT or LONG stirrin...

Страница 14: ...C91 Actual value correction must then be adjusted at programming level Memory fault Faulty regulator Remove the regulator and send it for repair Measurement range exceeded The maximum measurement ran...

Страница 15: ...However in practice this is possible only with difficulty as even a normal contactor without interference suppres sion produces interference pulses of up to 3 0 kV For this reason we recommend that t...

Страница 16: ...example be limited by using self induction diodes varistors or suppresser diodes The diagram on the left shows one possibility using a self induction diode AC voltage In the case of a c voltage interf...

Страница 17: ...he use of zero voltage switches is also recommended The suggestions made represent only a few of the possible ways of protecting a microprocessor controlled regulator system from interfer ence The sug...

Страница 18: ...0 1691 627200 Fax 44 0 1691 627222 Email sales fabdec com Fabdec GmbH Gerhardstrasse 5 45892 Gelsenkirchen Germany Tel 49 0 209 700 900 Fax 49 0 209 70090 20 Email germany fabdec com Fabdec LLC Octobe...

Отзывы: