Programming level 
operation

T2

T1

Hysteresis
for T2

Hysteresis
for T1

Target temperature

Target temperature

The programming level is for setting the regulatory parameters. 
Access to this level is more complex in order to avoid accidental 
resetting of the values by the end user.

Switching to programming level:

!

Press button 

Arrow UP

 and 

Arrow DOWN

 simultaneously 

for approx. 5 seconds.The first parameter [C1] appears in 
the display.

!

Press button 

Arrow UP

 and 

Arrow DOWN

 until you reach 

the parameter you want to adjust.

Meaning of parameters

Parameter C1:   Target temperature for T1

Parameter C2:   Target temperature for T2

The target temperature is the temperature at which the corre-
sponding relay contact is to be activated.

Parameter C10:   Hysteresis for target temp. 1

Parameter C11:   Hysteresis for target temp. 2

The hysteresis determines how much the milk temperature may 
deviate from the target temperature before the cooling com-
pressor is switched on. See sketch.

Parameter C20:   Duration of afterstirring

Duration (sec.) for which the stirrer runs after the compressor 
has switched off.

 

Parameter C21:   Duration of pause

Duration (min.) until the stirrer is switched back on after being 
turned off.

 

Parameter C50:   Duration of SHORT intermittent stirring

Duration (min.) of stirring after short pressing of the "intermittent 
stirring" button.

 

Parameter C51:   Duration of LONG intermittent stirring

Duration (min.) of stirring after longer pressing of the "intermit-
tent stirring" button.

Parameter C91:   Sensor correction

The sensor reading can be provided with a corrector which 
works cumulatively over the entire measurement range.

See also the section on "sensor installation" Page 14.

Parameter C99:   Button lock

Alteration of the target temperatures in the working level can be 
blocked by setting the button lock.

0 = lock off

1 = lock on.

C1

C2

C10

C11

C20

C21

C50

C51

C91

To change to programming level =

Press for 5 seconds simultaneously,
until parameter C1 appears.

Target temperat. 
for T1

0

10 mins.

2 mins.

20 mins.

120 sec.

0,7 K

0,7 K

Hysteresis for 
target temp. 1

Hysteresis for 
target temp. 2

Duration of
afterstirring

Duration of "short"
intermittent
stirring

Duration of "long"
intermittent
stirring

Sensor 
correction

Duration of
pause

Target temperat. 
for T2

C99

Button lock

Display

setting

Altering

setting

Factory

setting

Press SET and
     or simul-
taneously

Press

SET

button

Operating overview for programming level

SET

or

SET

or

To switch back to the working level:

Press for 5 seconds simultaneously

(Switches back automatically after 30 seconds.)

STOP

SET

4°/8°

Содержание Dari-Kool 720012

Страница 1: ...2016 Installation and Operation Manual Control for milk cooling tanks COMPACT KOOL...

Страница 2: ...ion Page 9 Programming level operation Page 10 Configuration level operation Page 11 Intermediate stirring options during cooling Page 13 Continuous stirring in OFF mode Page 13 Setting the actual val...

Страница 3: ...pressing a button Cooling mode Press the 4 8 button the compressor and agitator operate automati cally In between cooling periods agitator and compressor LEDs off intermediate stirring can be activat...

Страница 4: ...ce must not be installed in potentially explosive atmospheres The control cabinet for milk cooling tanks fulfils the EC requirements for electromagnetic compatibility EMC and the Low Voltage Directive...

Страница 5: ...it is necessary to shorten or lengthen the sensor cable on installation or if a sensor other than the one supplied is to be fitted the actual value correction parameter must be adjusted accordingly S...

Страница 6: ...itching contactor and motor protection switch 2 make contacts 16A AC 1 250 V 13 mm LED Display 3 digits 0 1 C 1 0 C two step controller 50 150 C 0 1 to 99 9 K free adjustable standard adjusting 0 7 K...

Страница 7: ...of the regulator are set As subsequent interventions by the end user after the parameters have been set can result in dangerous chan ges to functions which might not be immediately obvious access to t...

Страница 8: ...kly Release button SET To store the changed parameter in the memory first release the arrow button and then button SET Switching back to working level possible from any parameter Press button Arrow UP...

Страница 9: ...ds or downwards Button Agitator in cooling mode press for appr 1 sec SHORT intermediate stirring press for appr 3 sec LONG intermediate stirringSee also the section describing the intermediate stirrin...

Страница 10: ...n after being turned off Parameter C50 Duration of SHORT intermittent stirring Duration min of stirring after short pressing of the intermittent stirring button Parameter C51 Duration of LONG intermit...

Страница 11: ...he hysteresis is always upwards In the case of heating contacts it is below the target temperature cooling or heating contact is set at configuration level In the symmetrical hysteresis mode the value...

Страница 12: ...g of minimum pause time for compressor relay contacts K1 in order to prevent repeated switching on and off Range 0 0 999 seconds Parameter P80 Switch from target temperatur T1 to T2 Setting of funktio...

Страница 13: ...diately otherwise Intermediate stirring LONG will be activated Intermediate stirring LONG Press agitator button for approx 3 secs until Lon appears in the display The duration of SHORT or LONG stirrin...

Страница 14: ...C91 Actual value correction must then be adjusted at programming level Memory fault Faulty regulator Remove the regulator and send it for repair Measurement range exceeded The maximum measurement ran...

Страница 15: ...However in practice this is possible only with difficulty as even a normal contactor without interference suppres sion produces interference pulses of up to 3 0 kV For this reason we recommend that t...

Страница 16: ...example be limited by using self induction diodes varistors or suppresser diodes The diagram on the left shows one possibility using a self induction diode AC voltage In the case of a c voltage interf...

Страница 17: ...he use of zero voltage switches is also recommended The suggestions made represent only a few of the possible ways of protecting a microprocessor controlled regulator system from interfer ence The sug...

Страница 18: ...0 1691 627200 Fax 44 0 1691 627222 Email sales fabdec com Fabdec GmbH Gerhardstrasse 5 45892 Gelsenkirchen Germany Tel 49 0 209 700 900 Fax 49 0 209 70090 20 Email germany fabdec com Fabdec LLC Octobe...

Отзывы: