2.4 ELECTRICAL WIRING
To connect the bollard, use a multi-pole cable such as
FG7OR-0.6/1kV-
16G1.5 (16 wires of 1.5mm2) between bollard and control board
and a
FG7OR-0.6/1kV-3G4 cable (3 wires of 4 mm2) for the motor power supply,
both
measuring a maximum of 50 metres in length.
The cables must be laid inside a sheath of Ø50mm and passed through
the cable guides provided on the pit sheet (
8
-
1
) and through the
two corrugated conduits supplied with the pit.
Pass the wires through on the guides on the bollard frame as per as
8
-
2
then connect the corrugated conduits to the supports on the
bollard frame, as indicated in
8
-
3
.
Complete the electrical connections in the terminal box at the side
of the bollard as shown in
14
.
Any additional accessories (e.g. Open/close buttons, etc.) that are
connected to the control board must be double insulated.