9
ENGLISH
Ph
CLOSING PHOTOCELLS:
Enable this function is you want the closing photocells
to stop movement or reverse it at disengagement. If
this function is excluded, normally the tripping of the
photocells at closure causes the leaves to reverse
immediately.
Y
= reversal at disengagement
no
= immediate reversal at opening
no no no no no no
Ad
ADMAP FUNCTION:
This is used to activate operation according to French
regulations NFP 25/362.
Y
= active
no
= excluded
no no no no no no
Display
Function
Default
0
Default
1
Default
2
Default
3
Default
4
Default
5
o1
OUT 1:
used for setting the OuT output (open collector N.O.):
00
= Always active
01
= FAIL-SAFE
02
= INDICATOR LIGhT (off when closed, lighted during
opening and open/pause, flashes during closing)
03
= COuRTESY LIGhT (see next parameter)
04
= ALARM on BATTERY operation
05
= gate OPEN or in PAuSE
06
= gate CLOSED
07
= gate MOVING
08
= gate in EMERGENCY status
09
= gate OPENING
10
= gate CLOSING
11
= ELECTRIC LOCK command before CLOSuRE (you
have to interface with relay 24V – 00mA)
12
= safety device ACTIVE
13
= ‘TRAFFIC LIGhTS’ function (activates during OPENING
and when gate OPEN)
14
= timed output; it can be activated from the second
radio channel OMNIDEC (see next parameter)
15
= this output can be activated from the second
radio channel OMNIDEC (step-by-step function)
16
= electric lock before an OPENING (you have to
interface with relay 24V – 00mA)
Other more detailed programming
possibilities are feasible by programming
with a PC (see dedicated instructions).
00 00 00 00 00 00
t1
TIMING OUT 1 (only visible if at the previous step
o1
the
item
03
-
11
-
14
-
16
was selected):
Adjusts the timing of output OuT if a timed function from
1
to
99
minutes in -minute step was selected for the
functions
03
-
14
and from
1
to
99
seconds in -second
step for the functions
11
-
16
.
02 02 02 02 02 02