7.13 INPUT J1 WIRING CONFIGURATIONS
Pin 1 (Emergency) is connected to pin 6 (GND).
No other connection is present.
A three-position switch is supplied with the AIRSLIDE air curtain to
control the fan connected to connector J1.
A three-position switch connected between pin 2 and pin 3 can be
used to manage speeds V1 and V2 and to pin 6 GND.
Pin 2 corresponds to speed V1 selected via the DIP switch SW2 .
Pin 3 corresponds to speed V2 selected via the DIP switch SW1 .
Speed V2 can also be managed automatically via pin4 and pin5.
To use this in the event that the three-way selector is also used, it must
be connected to pin3 (V2).
Connect pin4 to pin6 GND.
■
Configuration 1
Wiring of the three-way switch, with indications of where it is
possible to manage the two speeds V1 and V2 as programmed
by the DIP switches SW1 and SW2
30
:
■
Configuration 2
In the event that the three-way switch is not used and automatic speed
management is used via inputs I1 and I2.
These inputs are NO (normally open) and manage speed V2.
When these inputs I1 and I2 close,
the speed of the fan moves from speed V2 to speed V1.
In this configuration, connect pin3 to pin6.
31
Management of the inputs can be via the automatic door board using
outputs O1 and O2.
Example of connection between board E1SL and board E1AS
O1 must be programmed on the E1SL board with the parameter
6=Door not closed and O2 with the parameter 11 = At least one safe
closing device active.
When input O1 switches from NO (normally open) to NC (normally
closed) the selected speed V2 will be activated.
When input O2 switches from NO (normally open) to NC (normally
closed) the selected speed V1 will be activated.
speed V1 will remain active as long as the safety device is engaged.
When this condition is no longer present, the the fan will return to
speed V2.
Connect pin3 to pin6 GND.
32
■
Configuration 3
This configuration provides for the three-way switch to be connected
to pin 2 and pin 3.
An NC button on pin 1 is used to manage an emergency command
to lock operation of the AIRSLIDE air curtain in NO (normally open)
configuration.
Two NO contacts on pin 4 and pin 5 to manage the speed of the fan
via external commands.