manualshive.com logo in svg
background image

31

ENGLISH

Table 8

NO.

LEDS

FAILURE

NOTE

1

2

3

4

5

(*)

1

ON

OFF OFF OFF OFF

Motor fault

B

2

OFF ON OFF OFF OFF

Governor and brake fault

B

3

ON

ON OFF OFF OFF

Initialisation process not possible

B

Opening angle insufficient

4

OFF OFF ON OFF OFF

Initialisation process not possible

B

Opening angle excessive

5

ON

OFF ON OFF OFF

Friction or spring load excessive

B

6

OFF ON ON OFF OFF

Spring load insufficient

B

7

ON

ON ON OFF OFF

Motor overload

B

8

OFF OFF OFF ON OFF

Encoder fault (disconnected

B

or in short circuit)

9

ON

OFF OFF ON OFF

Cut-off relay fault

B

10

OFF ON OFF ON OFF

EPROM / RAM / relay fault (automatic

B

control)

11

ON

ON OFF ON OFF

Short circuit on 24 V (960MP electronic

B

control unit or external)

12

OFF OFF ON ON OFF

Monitoring microswitch fault

A

13

ON

OFF ON ON OFF

Electric lock fault

B

14

ON

ON ON ON OFF

Power supply insufficient (< 140 V)

B

15

OFF OFF OFF OFF ON

Microprocessor fault

B

16

ON

OFF OFF OFF ON

Incorrect “door closed” position

A

17

OFF ON OFF OFF ON

Microprocessor alarm

B

18

ON

ON OFF OFF ON

“Double swing door”

A

communication error

9. SPECIAL APPLICATIONS

9.1. INTERLOCK

The programmable interlock function makes it possible to
interlock the operation of two doors so that the opening of one
is dependent on the closing of the other and vice versa.

Electrical connections

Connect the two automations to the same power supply
line.

Connect the X2 terminal strips of the two 960MP electronic
control units to each other, as shown in Figure 26.

Connect the control devices and the emergency
command, if present, as shown in figure 27.

The emergency command makes it possible for the two doors to
open or close simultaneously, depending on the programming
performed on the CODIS (see Table 7, function 5).

Note

: the control devices must be connected 

only

 to the KEY

input (see figure 27).

Programming and selection of operating function

To enable the interlock operation, the appropriate
programming of the following Level III functions must be
performed (see paragraph 8.3):

Function 3

: select the 

Interlock output

 option on both the

CODIS programming units (LED 6 lights up).

Function 4

: select the 

MASTER

 option on the CODIS unit of

the inner door (LED 6 lights up); select the 

SLAVE

 option on

the CODIS unit of the outer door (LED 6 goes out).

Function 16

: select the desired option on both the CODIS

programming units.

IMPORTANT: the interlock operation is activated only if the
NIGHT or ONE-WAY operating function has been selected on
both the CODIS programming units 

(see paragraph 8.1).

9.2. DOUBLE SWING DOOR

The programmable “double swing door” function makes it
possible to synchronise the movement of the two leaves that
face each other (see figure 29). For a correct operation of the
system, the opening of one leaf must be anticipated and its
closing must be delayed.

Note:

 the difference between the opening angles of the two

leaves must not exceed 20

°

.

Electrical connections and programming

-

Connect the X2 terminal strips of the two 960MP electronic
control units to each other, as shown in figure 28.

-

Connect the internal and external control devices, the
emergency command, if present, and the electric lock to
the electronic control unit  of the MASTER automation  (see
fig. 29).

Note

: the MASTER automation actuates the leaf whose opening

X2

24 25

X2

24 25

Fig. 27

Fig. 26

X2

CHIA

VE 

X2

11 12

OV

AC

CHIA

VE

CH;/D'EMERGENZA

15

22

25

N.O.

N.C. (N.O.)

N.C. (N.O.)

11 12

15

22

25

OV

AC

CH;/D'EMERGENZA

N.O.

EMERGENCY CL./OP

.

KEY

OVdc

N.C.

(N.O.)

EMERGENCY CL./OP

.

KEY

OVdc

(*)

A

: this error condition does not inhibit the operation of the system.

B

: this error condition inhibits the operation of the automation unit until

the fault has been eliminated.

FUNCT.NO.

LEDS

FUNCTIONS

LED 6

1

2

3

4

5

3

ON ON OFF OFF OFF

Gong output (terminal 24-960MP)

OFF

Interlock output (terminal 24-960MP)

ON

4

OFF OFF ON OFF OFF

SLAVE (interlock)

OFF

MASTER (interlock)

ON

16

OFF OFF OFF OFF ON

Opening commands stored

OFF

(interlock)

Opening commands not stored

ON

(interlock)

If the 

Opening commands stored

 option has been selected

(LED 6 unlit), it is not necessary to wait for one of the doors to
close before controlling the opening of the other.
When the closing of the first door has been completed, the
second door opens automatically.
If the 

Opening commands not stored

 option has been selected

(LED 6 lit) it is necessary to wait for one of the doors to close
before controlling the opening of the other.
Opening commands given during the operating cycle of the
first door will have no effect.

Table 9 indicates the functions to be programmed.

Table 9

Содержание 961 B-E

Страница 1: ...ubsequent amendments 91 368 EEC 93 44 EEC and 93 68 EEC complieswiththeessentialsafetyrequirementsinthefollowingEECDirectives 73 23 EEC and subsequent amendment 93 68 EEC 89 336 EEC and subsequent ame...

Страница 2: ...with an opening distance of the contacts of 3 mm or more Alternatively use a 6A thermomagnetic breaker with multi pole switching 12 Ensure that there is a differential switch up line of the electrica...

Страница 3: ...automatic unit for swing doors is a one piece unit consisting of an electromechanical device that allows door opening to be controlled by means of a driving arm The door is re closed by a spring syst...

Страница 4: ...the operator transmission shaft by means of the extension and the screw 4 provided fig 5 The arm must be mounted perpendicular to the closed door N B If a greater distance between the operator and the...

Страница 5: ...nitialisation procedure which includes setting the following parameters measuring the mass of the door determining the end stop positions determining the point at which the STOP safety device interven...

Страница 6: ...buzzer which emits sequences of acoustic signals corresponding to different statuses of the system The statuses that have occurred and their identification sequence can be seen in Table 6 Table 6 Aco...

Страница 7: ...contacts 11 12 13 14 15 16 EMERGENCY CLOSURE OPENING STOP SAFETY CLOSURE SAFETY 24 Vdc 0 Vdc 0 Vdc INTERNAL COMMAND 0 Vdc 8 9 10 EXTERNAL COMMAND 0 1 2 230 V 6 10 50 60 Hz 1 2 3 white brown green 0 V...

Страница 8: ...then re closes after the pause time POSITION 0 MANUAL NIGHT The position 0 can be used to select two different operating functions according to the programming carried out on the 961 B E programming u...

Страница 9: ...mme and monitor the operation of the system If the CODIS is used permanently it is necessary to activate function 7 at Level III programming functions see paragraph 8 3 For the electrical connection o...

Страница 10: ...L III PROGRAMMING FUNCTIONS The CODIS has a programming level where certain functions can be selected These functions are required for several special applications Note a voltage drop or a RESET comma...

Страница 11: ...n N O contact terminals 18 19 960MP Door open closed indication N C contact the open and closed positions of the door are indicated by the opening of a N C contact terminals 18 19 960MP function 12 Al...

Страница 12: ...the inner door LED 6 lights up select the SLAVE option on the CODIS unit of the outer door LED 6 goes out Function 16 select the desired option on both the CODIS programming units IMPORTANT the interl...

Страница 13: ...th the door closed draw a vertical line on the spring as shown in figure 30 Open the door and check the state of the line figure 30 shows two possible configurations In case B fig 30 lubricate the spr...

Страница 14: ...mains open o LED 4 AUTOMATIC The door opens when internal or external commands are active and re closes after the pause time o LED 3 AUTOMATIC SPARE o LED 2 ONE WAY Entry or exit inhibited only one di...

Отзывы: