5.4.2.
J7 Terminal board - Power supply (fig. 23)
POWER SUPPLY (terminals PE-N-L):
PE:
Earth connection
N :
Power supply ( Neutral )
L :
Power supply ( Line )
NB.:
For correct operation, the board must be connected to
the earth conductor in the system. Install an adequate
differential thermal breaker upstream of the system.
To install several partial opening pulse generators,
connect the N.O. contacts in parallel (fig.35).
FSW OP - Opening safety devices contact (terminal 3):
The
purpose of the opening safety devices is to protect the
leaf movement area during opening. During opening, in
the
A-AP-S-E-EP
logics the safety devices reverse the
movement of the gate, or stop and restart the movement
when it is released (see advanced programming in
Chpt. 5.5.2). During the opening cycle in logicsthe
B, C
and
B/C
, they interrupt movement. They never operate
during the closing cycle.
If the
Opening safety devices
are engaged when the
gate is closed, they prevent the opening movement.
To install several safety devices, connect the N.C.
contacts in series (fig.25).
NB.: If no opening safety devices are connected, jumper
connect inputs FSW OP and -TX FSW
(fig. 26).
FSW CL - Closing safety devices contact (terminal 4):
The
purpose of the closing safety devices is to protect the
gate movement area during closing. During closing, in
the
A-AP-S-E-EP
logics, the safety devices reverse the
movement of the gate, or stop and reverse the
movement when it is released (see advanced
programming in Chpt. 5.5.2). During the closing cycle in
logics
B, C
and
B/C
, they interrupt movement. They
never operate during the opening cycle. If the
Closing
safety devices
are engaged when the gate is open,
they prevent the closing movement.
To install several safety devices, connect the N.C.
contacts in series (fig.25).
NB.: If no closing safety devices are connected, jumper
connect terminals FSW CL and -TX FSW
(fig. 26).
STOP
- STOP contact (terminal 5):
any device (e.g. a push-
button) which, by opening a contact, stops gate
movement.
To install several STOP devices, connect the N.C.
contacts in series (fig. 25).
NB.:
If STOP devices are not connected, jumper
connect the
STOP
and
-
terminals.
SAFE -
EDGE safety device contact (terminal 6):
The purpose of
the "edge" safety device is to protect the leaf movement
area during opening/closing. In all logics, during opening
and closing, the safety device reverses gate movement
for 2 seconds. If the safety devices operate again during
the 2-seconds reversing time, it stops movement (STOP)
without any reversing.
If the
Edge safety device
is engaged while the gate is
closed or open, it prevents movement.
To install several safety devices, connect the N.C.
contacts in series (fig.25).
NB.: If edge safety devices are not connected, jumper
connect the SAFE and - inputs
(fig. 26).
–
Negative for power supply to accessories (terminals 7
and 8)
+
24 Vdc - Positive for power supply to accessories
(terminals 9 and 10)
Important:
Accessories max. load is 500 mA. To calculate
absorption values, refer to the instructions for individual
accessories.
Connection of a pair of closing photocells and a pair of
opening/closing photocells
Connection of two N.O. contacts in parallel
(e.g. Open A, Open B)
5.4.3.
J6 Terminal board - Motors and flashing lamp
(fig. 23)
MOTOR - (terminals MOT-C, MOT-1, MOT-2):
Motor connection
(see Par. 6.5).
LAMP - (terminals LAMP L, LAMP N)
: Flashing lamp output 230Vac
max 60W.
5.4.4.
J1 Terminal board - Accessories (fig. 23)
Consult the relevant tables for a detailed description of
operation in the different logics
OPEN A - “Total Opening” command (terminal 1):
any pulse
generator (push-button, detector, etc.) which, by
closing a contact, commands total opening and/or
closing of the gate leaf.
To install several total opening pulse generators,
connect the N.O. contacts in parallel (fig. 35).
OPEN B - “Partial opening” or “Closing” command (terminal 2):
any pulse generator (push-button, detector, etc.)
which, by closing a contact, commands partial
opening and/or closing of the gate leaf. In the
B, C
and
B/C
logics, it always commands gate closure.