AC Power Wiring Guidelines
1. Check local wiring codes in all cases and follow all
local building codes. Wiring and hookup should be
performed by qualified electricians/installers only.
2. AC power should be supplied from a circuit breaker
panel and must have its own dedicated circuit breaker.
This supply must include a green ground conductor.
3. Properly ground the gate operator to minimize or
prevent damage from power surges and/or lightning.
Use a grounding rod if necessary. A surge suppressor is
recommended for additional protection.
BLACK
RED (230V)
GREEN
WHITE
115V LINE
115V LINE
GROUND
NEUTRAL
115 V
230 V
TX
TX
RX
RX
PHOTO
OP
OPEN
DEVICES
PHOTO
CL
24VDC
RX PHOTO
24VDC
TX PHOTO
+ -
+ -
SHADOW
INPUT
TEST
BUTTON
24VDC
RX PHOTO
24VDC
RX PHOTO
a b
a b
PHOTO
OP
a
b
a
b
OPEN SAFETY MONITORED
CLOSE SAFETY MONITORED
-
+
-
+
PHOTO
CL
Monitored safety connections
The prewired enclosure comes with dedicated terminal
blocks for the connection of safety photocells that can be
monitored by the control board for presence and correct
operation.
Connect the trasnsmitter photocells as shown on the draw-
ing, to the dedicated TX photo outputs. Connect the receiver
photocells 24V power to the dedicated outputs on the
terminal block as shown. Connect the N.C. outputs of the
photocells to the dedicated terminal blocks.
IMPORTANT: To enable monitoring of the photocells make
sure that FAIL-SAFE mode is turned on in the advanced pro-
gramming menu:
F
+
+
ADVANCED PROGRAMMING
FAIL SAFE:
If this function is activated, it enables a
function test of the photocells before any
gate movement. If the test fails (photocells
not serviceable), the gate does not start the
movement.
= Active
= Disabled