background image

eyePower PDU User Manual V1.0.docx 

Page 2 of 6 

Features: 

Inlets / Outlets 

Single or dual changeover inlets fitted with 16A powerCON. The unit is rated for 16A total, no need for a front panel 
breaker which would affect fusing discrimination with the upstream 16A supply. Fourteen 10A IEC outlets are fitted, 
together with dual supply, RS422/485, Ethernet and external sensor connections are on the rear panel. 

Internal Distribution 

eyePower Limited PDU do not rely on PCB tracks for power distribution, all units are hand wired with crimped 
cables and soldered busbars. Installation fault currents can be surprisingly high, a 10A fuse can pass 30A for 30 
seconds worst case. I2R heating of the distribution is then 9 times higher than normal running. PCBs can be 
damaged in this time with failure possibly in the long term rather than immediate. Even for short circuits connected 
to the unit, technical installations often have low loop impedances with high fault currents of kA that the distribution 
must withstand before the fuse ruptures.  

Fusing 

Outlets are 10A rated to the unit maximum of 20A. Factory fit is 3.15A fuses which suits most loads and provides 
clear discrimination between supply and outlet fusing. Customers can uprate fuses as required to maximum 10A.  

Relay Switching 

Relays are high quality, 20A rated with a tagged output wired direct to the 10A IEC outlets. Standard relays are 
preferred, this latest unit reduces relay power consumption and heating by 70%. Relays hardly get warm using 
PWM, a technique now favoured in the automotive industry to save energy. 

Voltage Presence Detect 

Supply voltage is detected after each fuse and after each relay, using a circuit which consumes 0.25W total for 
over 30 measurements. Some other designs consume this much power for each presence detect and do not check 
both fuse and relay. 

Current Measurement 

Current measurement is performed with high sensitivity current transformers. Unlike cheap, PCB mounted shunt 
resistors there are no heating issues and reliability is maintained by simply passing the outlet cable through the 
centre of the transformer rather than routing via PCB. With no direct connection to the supply, there are no issues 
when measuring current throughout supply voltage disturbances. Currents from mA to 40A (70A peak) can be 
monitored. 

1-Wire

 Sensors 

Dallas/Maxim sensors can be connected. Sixteen are supported for local connection, allowing for temperature, 
humidity and GPIs in addition to the standard four GPIs if required. 

Macro Programs 

eyePower PDU have at their core user programmable sequences for outlet and GPI interactions. This gives the 
web interface access to complicated sequences to meet any requirement. Even the front panel switch can access 
these macro routines, so the switch is extremely versatile. The unit can also redefine GPI and switch use according 
to live requirements. 

Содержание PDU

Страница 1: ...wer PDU User Manual Version 1 0 15th December 2021 SAFETY NOTICE End users must be made aware that power outlets are remote controlled This unit is not certified for safety isolation of the electrical supply ...

Страница 2: ...put wired direct to the 10A IEC outlets Standard relays are preferred this latest unit reduces relay power consumption and heating by 70 Relays hardly get warm using PWM a technique now favoured in the automotive industry to save energy Voltage Presence Detect Supply voltage is detected after each fuse and after each relay using a circuit which consumes 0 25W total for over 30 measurements Some ot...

Страница 3: ...tly OLED Display A full colour front panel display allows menu driven access to unit status that will change over time to meet users needs Ethernet Custom developed 10 100Mbit Ethernet module with PoE as standard that can power the entire unit and provide status data through power failure or brown out The powerful 32 bit processor will meet the demands of future developments There is a software ro...

Страница 4: ...et changeover versions eyePower changeover PDU have two inlets which are labelled A B Failure of A will cause changeover to B On return of A when both supplies have been stable for ten seconds and the two supplies are synchronous for one mains zero crossing an eyePower PDU will change back to A automatically Note this delay can be changed using eyePower Limited s Windows software via the serial po...

Страница 5: ...Live Neutral reversed This can be checked by looking at the Neutral Earth reading on the OLED display Input i or to scroll to Neutral Earth reading On a changeover PDU the display will alternate between A supply and B Supply readings 2 The PDU does not have a good earth Preferred Supply eyePower PDU are designed for use on two synchronous and phase coherent supplies The A supply is preferred in th...

Страница 6: ...eatly minimise the change of arcing between supplies all input and output relays are briefly opened hence a total of nineteen relays operate at the same time Notes THIS UNIT MUST BE EARTHED THIS UNIT IS DESIGNED FOR EUROPEAN STANDARD TYPE TN MAINS WITH NEUTRAL NEAR TO SAME POTENTIAL AS EARTH 220V 240V NOMINAL INLETS ARE 16A AND ALL INTERNAL WIRING IS RATED FOR 20A MAXIMUM UPSTREAM SUPPLY MUST BE F...

Отзывы: