IPL EXP I/O Series • Hardware Features and Installation
21
Relay ports
The IPL EXP 200 and IPL EXP RIO8 have relay ports, which also provide control for power,
screen or projector lifts, window coverings, and similar items, when trigger events occur.
RELAYS
+V +S -S
RELAYS
1 2 C
1 2 3
IR/S
S G
1 2 12V24V G
3 4 12V24V G
+V OUT / DIGITAL I/O
5 6 12V24V G
7 8 12V24V G
12 VDC / 24 VDC
19W MAX TOTAL
IPL
3
4
1
2
7
8
5
6
RELAYS
Rear Panels
IPL EXP RIO8
Front Panel
Normally Open (2)
Common
Normally Open (1)
Common
To Room
Control
Equipment
To Room
Control
Equipment
Closed
Normally
Open
2
1
C
2
1
C
Relays
• Connect devices for contact control.
• Do not exceed a total of 24 V at 1 A for each port.
or
Common
Relay 2
Relay 1
All relays
are
normally
open.
Relay LEDs
Light when the corresponding relays
are activated (tied to GND, closed).
Figure 10.
Cabling Relay Ports
These relay contacts may be used to control any equipment as long as the contact
specifications of a total of 24 V at 1 A are not exceeded for each port. These relays are
normally open by default.
When activated, the open contacts close. They can be set up to operate in one of two
ways:
•
Latching
(brief or indefinite period contact) (press to close, press to open), or
•
Pulsed
(timed cycle) (press to close, timeout to open, with automatic repeat).
In pulse mode the default timeout period (hold time) is ½ second (500 ms). Use Global
Configurator to change the length of the timeout period.
NOTE:
The pulse function is absolute: it always sets the relay state to closed, times
out (briefly), then opens the contact. It overrides the previously selected setting (on
state, off state, or toggle).