background image

 Model 380360 Version 1.7 September 2003 

 

Support Hotline (781) 890-7440 

Tech support: Ext. 200; Email: [email protected] 

Repair/Returns: Ext. 210; Email: [email protected] 

Website: www.extech.com 

Application Note for Large Installations 

In large wiring installations where the insulation of outlets is being tested, more than one 
insulation resistance measurement may have to be made to take into account parallel 
resistances. Divide large systems into subgroups and test subgroups individually. Also, in 
large installations, the capacitance of the insulation will be high, thereby taking longer to 
charge when being tested. Care must be taken not to finish a measurement until the 
insulation capacitance is fully charged (a steady, stable reading is an indication that this is 
the case). Be careful not to turn the range switch while the test button is pressed. 

Repair and Calibration 

Extech offers repair and calibration services for the products we sell. Extech also provides 
NIST certification for most products. Call the Customer Service Department for information 
on calibration services available for this product. Extech recommends that annual 
calibrations be performed to verify meter performance and accuracy. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Warranty 

EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects in parts and workmanship for one 

year from date of shipment (a six month limited warranty applies on sensors and cables). If it should become necessary to 

return the instrument for service during or beyond the warranty period, contact the Customer Service Department at (781) 

890-7440 ext. 210 for authorization or visit our website at www.extech.com (click on ‘Contact Extech’ and go to ‘Service 

Department’ to request an RA number). A Return Authorization (RA) number must be issued before any product is returned 

to Extech. The sender is responsible for shipping charges, freight, insurance and proper packaging to prevent damage in 

transit. This warranty does not apply to defects resulting from action of the user such as misuse, improper wiring, operation 

outside of specification, improper maintenance or repair, or unauthorized modification. Extech specifically disclaims any 

implied warranties or merchantability or fitness for a specific purpose and will not be liable for any direct, indirect, incidental 

or consequential damages. Extech's total liability is limited to repair or replacement of the product. The warranty set forth 

above is inclusive and no other warranty, whether written or oral, is expressed or implied. 

 
 
 

Copyright © 2003 Extech Instruments Corporation. All rights reserved 

including the right of reproduction in whole or in part in any form. 

Содержание 380360

Страница 1: ...ongratulations on your purchase of Extech s Insulation Tester Megohmmeter The Model 380360 provides three test ranges plus continuity and an AC voltage test A handy 3 minute test lock feature and a data hold switch are also included This professional meter with proper care will provide years of reliable service ...

Страница 2: ... insulation 6 When servicing use only specified replacement parts International Safety Symbols Caution refer to this manual before using this meter Dangerous Voltages Meter is protected throughout by double or reinforced insulation Specifications General specifications Display 0 65 3 1 2 digit 2000 count LCD Sampling rate 2 5 readings per second Test ranges 2000MΩ 1000VDC 200MΩ 500VDC 200MΩ 250VDC...

Страница 3: ...ircuit Volt Overload Protect 200Ω 0 1Ω 100Ω 3 3V 500Vrms AC VOLTAGE Range Res Accuracy Input impedance Overload Protect 600VAC 1V 0 8 3d 10MΩ 750Vrms MEGOHMMETER RANGES Range Res Accuracy Terminal voltage 200MΩ 250VDC 250V 10 0 200MΩ 500VDC 0 1MΩ 500V 10 0 0 to 1000MΩ 1000VDC 3 5d 1000 to 2000MΩ 1000VDC 1MΩ 5 5d 1000V 10 0 Range Test Current Load Short circuit Current 200MΩ 250VDC 250KΩ 200MΩ 500V...

Страница 4: ...rotary switch to the 200Ω range 3 Set the HOLD switch to the left off position and the MANU LOCK switch to the MANUAL position 4 Touch the test lead tips together 5 Press the red TEST button 6 Resistance should read less than 1Ω and the audio tone should sound 7 With the leads not touching the display should read 1__ indicating over range 8 Readings displayed other than the readings described abov...

Страница 5: ...to the HI input terminal black lead to the LO terminal 2 Set the rotary switch to the desired voltage test position 250V 500V or 1000V 3 Connect the tips of the test leads to the equipment under test 4 Set the MANU LOCK switch to the LOCK position 5 Press and release the red TEST button A 3 minute continuous test will begin The red TEST button can be pressed at any time to end the test If the TEST...

Страница 6: ...her end of the test leads to the circuit under test 4 Read the voltage value on the LCD Data Hold Function The Data Hold function freezes the displayed reading Move the HOLD switch to the rightmost position to freeze the displayed reading The H will appear on left side of the display when the meter is in the Data Hold mode Move the switch to the left position to exit the Data Hold mode the H indic...

Страница 7: ...nd the other lead to the brush on the commutator 3 If the resistance measurement indicates a weakness raise the brushes off of the commutator and separately test the armature field coils and brush rigging one at a time Leave one lead connected to the grounded motor housing while testing the motor components This also applies to DC Generators Testing Cables 1 Disconnect the cable under test from th...

Страница 8: ...CH INSTRUMENTS CORPORATION warrants this instrument to be free of defects in parts and workmanship for one year from date of shipment a six month limited warranty applies on sensors and cables If it should become necessary to return the instrument for service during or beyond the warranty period contact the Customer Service Department at 781 890 7440 ext 210 for authorization or visit our website ...

Отзывы: