24
2.13 ~AAO(Data)
Description:
Set Module Name
Syntax:
~AAO(Data)[CHK](cr)
~
delimiter character
AA
address of reading/response module (00 to FF)
O
command for set module name
(Data) new name for module, max 6 characters
Response:
Valid Command:
!AA
Invalid Command:
?AA
Example:
Command: ~01O9016
Receive: !01
Set address 01 module name to 9016, return success.
Command: $01M
Receive: !019016
Read address 01 module name, return name 9016.