8.Load Control
8.1 Fan
When you start or turn off the grill or when the grill is under high-temperature protective mode, the fan
will delayed for 10 minutes and the furnace temperature drops to 130
°
F before it is turned off.
8.2 Fire Rod
8.2.1 First Ignition
:
(
1
)
The starting temperature is higher than 165
°
F, ignition for 5 minutes, as long as the temperature is
still higher than 165
°
F, the ignition is successful.
(
2
)
The start-up temperature is less than 165
°
F, it needs to meet 50 degrees Fahrenheit higher than the
start-up temperature, or the temperature exceeds 165
°
F (the original temperature is lower than 165
°
F) are
considered to be successful.
(
3
)
The above conditions are not met for more than 13 minutes, the low temperature alarm Erl.
8.2.2Re-Ignition:
When set temperature less than 205
°
F for more than 32 seconds, the fire rod will restart at 70% of max
power; The fire rod will stop working after the temperature is higher than setting temperature for more than 32
seconds.
8.3Auger Motor
8.3.1
The feeding time of the feeding motor is: feeding 5 seconds -> not feeding 25 seconds -> feeding 60
seconds -> not feeding 60 seconds -> feeding 60 seconds -> not feeding 60 seconds -> feeding 60 seconds ->
not feeding 60 Seconds, total 6 minutes and 30 seconds, and the ignition is successful.It will exit the ignition
state. If after 6 minutes and 30 seconds the ignition still fails to meet the conditions for successful ignition, it
will enter the second ignition, the feeding period of the feeding motor is the same as the first ignition.
8.3.2
If the two ignitions are not successful, that is, after 13 minutes, the conditions for successful ignition are
still not met, an ErL error warning will be reported.
8.3.3
After the ignition is successful, start the smoke mode in the SMOKE file; start the PID feeding program
according to the specific temperature at 180~450
°
F, and control it according to the 500
°
F file in the high file