The service menu is built up in four levels:
Base settings for the
three applications
Menu level 1
Menu level 2
Menu level 3
Function
Default
3
Configuration
30
Exit settings
31
PDS/AUX config
1 = PDS, 2 = C-NO
2
(C-NO)
1 (PDS)
(Locked)
2
(C-NO)
32
Triac settings
320
Exit
321
U
min
Min. output voltage in % of 230 V AC, 35-100
%
35 %
N/A
35 %
322
U
max
Max. output voltage in % of 230 V AC,
35-100
%
100 %
N/A
100 %
33
0–10 V settings
(Not active)
330
Exit
331
U
min
Min. output voltage in % of 10 V DC,
0-100 %
0 %
N/A
0 %
332
U
max
Max. output voltage in % of 10 V DC,
0-100 %
100 %
N/A
100 %
34
Manual fan mode
340
Exit
341
Manual Fan mode
on/off
Switch Manual Fan mode on and off
OFF
OFF
OFF
342
Manual Fan mode
speed
Set the motor manually, 35–100 %
35 %
35 %
35 %
35
Regulation parameters
350
Exit
351
Amplification Xp
Set proportional amplification, 0.2 to 5
2,2
N/A
1,2
352
Integration time T
i
Set integration time from 1 to 30 s
5
N/A
3
353
Differential time T
d
Set differential time from 1 to 30 s
1
N/A
5
354
Sample time
Set sample time from 1 to 999 ms
300 ms
N/A
300 ms
4
Temperature sensor
40
Exit temperature sensor
41
Sensor ON/OFF
Sensor ON or OFF
OFF
OFF
42
Autostart/-stop
420
Exit
421
ON/OFF
Sensor ON or OFF
OFF
OFF
422
Start temperature
Set start temperature between 5-450 °C
40 °C
40 °C
423
Stop temperature
Set stop temperature between 0-445 °C
35 °C
35 °C
43
Pressure function
430
Exit
431
ON/OFF
Pressure function ON or OFF
OFF
OFF
432
Temperature limit
Set temperature limit between 5-450 °C
250 °C
50
44
Alarm
440
Exit
441
ON/OFF
Alarm ON or OFF
OFF
OFF
442
Temperature limit
Set temperature limit between 25-450 °C
450 °C
450 °C
443
Alarm delay
Set delay for temperature limit alarm
between 0-60 sec.
5
5
3120049-EBC10-UK
14
• Product information
14
• Product information