HC Controller
Unit
Fault code
Category
Unit
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of
dampers, sensors, air directions, etc.)
xx yy
z
16 02
1
HC
HCW: Fan speed tem-
porarily reduced
iHCW
: Fan speed temporarily reduced because warning lim-
it for frost protection of water heating coil has been reached
16 03
1
HCW: VEX temporarily
stopped
iHCW
: Fan speed temporarily reduced because stop tem-
perature for frost protection of water heating coil has been
reached
16 04
1
HCW: VEX stopped
iHCW
: Fan speed stopped because of frost alarm on the
water heating coil
16 05
1
HCE: Run-on operating
because electric heat-
ing coil warm in last
three minutes
HCE
: The fans run on for three minutes after the electric
heating coil has been in operation
CO
2
sensor
Device
Fault code
Category
Alarm description
Troubleshooting
(See appendix 1: "Simplified diagrams" for the positioning of dampers,
sensors, air directions, etc.)
xx yy
z
21 01
2
No modbus communi-
cation to MIO CO
2
module
● Check the modbus cable between the connection board (EX-
act)/main board (EXact2) and MIO module.
● Check the modbus cable from the MIO module to the other
units for faulty wiring.
● Check the DIP-switch settings in the MIO module, refer to MIO
module instructions.
21 02
2
CO
2
level below 100
ppm. CO
2
sensor may
be defective.
● CO
2
sensor may be defective and should be replaced.
21 03
2
CO
2
input via BMS se-
lected and BMS has
not been configured.
● Configure BMS.
3006401-2022-05-04
Alarms
59/72