Example
CO
2
concentration in the air
is ...
Airflow...
A
less than Start
is the same as set value
B
between Start and Maximum
increases gradually to a high level,
depending on the current CO
2
level
C
greater than Maximum
is increased to maximum air re-
placement
Menu 3.1.2.2 - Humidity compensation of airflow
Requirements
A humidity sensor (RHB, MIO-RH, BMS) must be fitted in order to be able to se-
lect humidity compensation of the airflow. The sensor must be installed in the
room in which you wish to make compensation, such as a bathroom. Connection
of the sensor is described in the additional instructions accompanying the sensor.
Function
When the control system is operating, this function increases airflow in the event
of increasing humidity levels.
Selecting humidity
compensation
Activate in Menu 3.1.2.2.