Line in Menu 3.4
Factory-set and
should not be
changed.
Comments
TS
Activation of external tempera-
ture sensor and selection of
type. Options:
● None
● TS ROOM
● TS DUCT
*)
*) Not applicable to VEX308
CO2
Activation of CO
2
sensor Op-
tions:
● None
● MIOCO2
● CO2B
● BMS
RH
Activation of RH sensor. Op-
tions:
● None
● MIORH
● RHB
● BMS
4.2 De-icing method
4.2.1 Bypass de-icing - example
Extract
air
Supply
air
Exhaust
air
Outdoor
air
RD13238GB-01
+18°C 100%
+14°C
+20°C
+22°C
-10°C
80%
100%
100%
20%
+
Ventilator 1
Ventilator 2
+3°C
Detection meth-
od
Principle
De-icing starts when...
Temperature con-
trolled
Temperature sensor T
ice
registers the temperature
in the heat exchanger and starts the de-icing proc-
ess when the indicated temperature is reached.
Temperature is below the set
value e.g. T
ice
< 0°C. (Menu 7.3)
3006401-2022-05-04
Starting up the unit for operation
17/72