Fault finding

Some systems call for a special starting 
procedure after fail-safe disconnection. Fol-
low this before pressing the RESET button 
(Fig. 7-B).

Observation

Type of fault

Solution

No light in SUPPLY (Fig. 7-I

A blown fuse or a failing power 
supply

1) Check the fuse (Fig. 7-J) and the chimney fan
2) Check the wiring

Permanent light in ALARM diode 
(Fig. 7-A)
-  The chimney fan light is off (FAN 

Fig. 7-D)

-  (It is only possible when MANUAL 

RESET is ON Fig. 7-C)

Grid failure (Power failure)

Press the RESET button for one second (Fig. 7-B) - 
PLEASE SEE THE WARNING.

Permanent light in ALARM diode 
(Fig. 7-A)
- The chimney fan light is on (FAN 

Fig. 7-D)

Failing chimney draught

1) If PDS light is on  (Fig. 7-E), press the RESET but-

ton for one second (Fig. 7-B) - PLEASE SEE THE 
WARNING.

2) If PDS light is off (Fig. 7-E), check the repair switch 

to the chimney fan

3) Check the flue, chimney and chimney fan for block-

ing

4) Check the commissioning according to item 2.4.

Flashing ALARM diode (Fig. 7-A)
-  (It is only possible when PDS 

CHECK is ON Fig. 7-C)

Failure in fail-safe supervision 
(PDS CHECK)

1) Check the setting of the fail-safe system. The natu-

ral draught can prevent disconnection. Alternatively 
deselect PDS-CHECK on dipswitch Fig. 7-C 

2) Check the connection to the fail-safe system
3) Check the change function of the fail-safe system

7

Содержание EBC11

Страница 1: ...EXHAUSTO 3001414 2000 02 01 fm 1 8 44 GB...

Страница 2: ...veloped to meet BS 5440 Part 1 1990 and BS 6644 1991 and other relevant European standards Functions When the boiler thermostat calls for heat the chimney fan will immediately start up on full speed W...

Страница 3: ...t 1 Opto coupler 10 230V 6 7 Boiler thermostat 1 Opto coupler 10 230V 8 24V DC supply for voltage free contact 9 LK0V DC supply for voltage free contact 10 Boiler thermostat 2 Opto coupler 10 230V 11...

Страница 4: ...connected over terminals 1 3 Connection to the boiler control Step 1 The normal start signal for the burner phase is connected to terminal 6 Loop terminals 7 and 14 The start signal for the boiler com...

Страница 5: ...cted over to terminal 6 Loop terminals 7 and 14 The start signal for the boiler comes on from terminal 15 Connect neutral from the timer to terminal 4 Neutral for the boiler can be taken from ter mina...

Страница 6: ...egistered click sound or the light Fig 6 D goes out Register the PDS value of disengagement Set the PDS to 25 Pa below the registered value of disengagement 7 2 step systems Start step 2 on the system...

Страница 7: ...SEE THE WARNING Permanent light in ALARM diode Fig 7 A The chimney fan light is on FAN Fig 7 D Failing chimney draught 1 If PDS light is on Fig 7 E press the RESET but ton for one second Fig 7 B PLEA...

Страница 8: ...Graben 40 D 55411 Bingen Kempten Tel 49 6721 9178 0 Fax 49 6721 9178 99 E mail exhausto sparkasse net www exhausto de EXHAUSTO NORGE A S Enebakkveien 117 N 0680 Oslo Tel 47 2268 9006 Fax 47 2268 0384...

Отзывы: