Power supply and inputs / outputs
Below you will find the minimum and maximum admissible values of digital inputs and outputs as well as
analog voltage and current inputs, and also cLAN consumption and power supply.
Power supply
cLAN-1520/cLAN-3524 in XF and MQ versions
Parameter
Condition
Minimum
Maximum
Units
Input voltage
10
30
Vdc
Average
consumption
@ 24 Vdc
@ 12 Vdc
100
190
mA
cLAN-1205/cLAN-2205 in XF and MQ versions
Parameter
Condition
Minimum
Maximum
Units
Input voltage
10
30
Vdc
Average
consumption
@ 24 Vdc
@ 12 Vdc
50
80
mA
cLAN-3404 in XF and MQ versions
Parameter
Condition
Minimum
Maximum
Units
Input voltage
10
30
Vdc
Average
consumption
@ 24 Vdc
@ 12 Vdc
90
170
mA
Digital inputs
To activate the digital inputs a continuous voltage must be applied externally. This source of power has to
share the GND terminal with the power supply of the equipment. If necessary the same power supply
that feeds the cLAN can be used. The input is of a Sinking type. It accepts sensor or PNP Sourcing type
devices.
cLAN-3524 in XF and MQ versions
Parameter
Minimum Maximum
Units
cLAN-MQ User Manual
Features of power supply and inputs/outputs
24 / 73
Содержание cLAN-MQ Series
Страница 14: ...2020 11 19 cLAN MQ User Manual cLAN Configurator 13 73 ...
Страница 22: ...Analog inputs cLAN MQ User Manual Physical Inputs Outputs 21 73 ...
Страница 30: ...2020 09 28 cLAN MQ User Manual Features of power supply and inputs outputs 29 73 ...
Страница 59: ...2020 11 20 cLAN MQ User Manual Scripts Publish Subscribe 58 73 ...
Страница 66: ...2020 09 28 cLAN MQ User Manual cLAN2205 MQ 65 73 ...
Страница 69: ...2020 09 28 cLAN MQ User Manual cLAN3404 MQ 68 73 ...