In addition to the Standard features offered by the XP family of inverters,
there are features specific to the charger and transfer switch functionality
Positive (+) and Negative (-) input terminals are
5/6" studs
with brass hardware. They are accessed under the rear cover. Use
Appendix A” to choose the appropriate gauge wire for your specific
model.
Provides the user with a remote method to turn the
inverter on and off. “REMOTE” connection is on the barrier terminal strip
located under the rear cover.
.
“
All domestic models have two NEMA - 20A receptacles
on the front plate and a barrier strip terminal on the backplane. They are
tied to the inverter
’
s output as well as the charger
’
s input, which means
that there will always be AC present on these outlets as well as the
“
LOAD” connections on the backplane. The AC will come from the
primary source when present and from the inverter when the primary
source is not present.
DC INPUTS:
REMOTE ON/OFF:
AC OUTPUTS:
.
.
.
S
tandard Features
2.0
supply it
’
s peak current to the load for 3 seconds then it will scale back
to it
’
s rated current for an additional 4 seconds. If the short is not cleared
within that 7 seconds the inverter will shut off requiring the user to cycle
the power button to turn it back on. Exeltech
’
s inverters can output their
full rated power continuously at 30° C (86° F). The inverter is derated
20% of its full power for every 10° C over 30° C. IE; 80% of normal
capacity at 40° C, 60% at 50° C . . . Etc.
.