The EXELTECH MCX/ICX Inverter/Charger has 1000 Watts of rated
DC power available to keep your batteries charged to their optimum
level, when power to run your critical load is available from a primary
source. However, when the primary source is interrupted, your
EXELTECH MCX/ICX stands ready to deliver 2000 Watts of rated power,
and 4000 Watts of surge power within 4mS. Then, once the primary
source of power has been restored, the Inverter/Charger will sense it’s
presence, lock on to it’s frequency, and seamlessly transfer your critical
load back to its primary source.
Many inverters are rated in Volt-Amps (VA), as opposed to Watts. This is
in an attempt to make an inverter or UPS (Uninterruptible Power Supply)
appear larger than it really is. The only fair way to
.
specify these products
is in watts (W), which is power the inverter can actually deliver. If
Exeltech inverters were specified in VA, our 2000 watt inverter could be
rated at 2500 VA @ 0.8 pf., 2857 VA @ 0.7 pf, or an incredible 4000 VA
@ 0.5 pf. It is confusing to specify a product in VA, because the power
factor must also be specified. Exeltech's inverters can output their full
rated power continuously at 30° C (86° F)
The inverter will maintain a spectrally pure output with any load, due to a
specially designed non-linear control loop in the primary DC to DC
converter. This circuitry is one of three circuits which protect the inverter
from any overload condition.
EXELTECH 2KW INVERTERS
These inverters can supply twice their rated output power for 3 seconds,
in order to start motors or supply in-rush currents to electronic loads. If
output power is exceeded for greater than 3 seconds, output voltage is
reduced to a level which will provide the inverter’s rated power to the load
by clipping tops of the waveform. Should the overload condition clear, the
inverter will again provide the cleanest Sine Wave in the industry. If the
overload condition persists, requiring the user to cycle the power button
to turn the inverter on again. The inverter will disable its output within 7
seconds. This over-current circuitry insures maximum current does not
exceed 200% of rated RMS current for XP-2000. The third protection
mechanism is short circuit. Similar to overload condition, the inverter will
.
.
.
Page 4
MCX/ICX INSTALLATION AND OPERATION MANUAL