Excalibur P95-2 Zero Clearance Direct Vent Gas Fireplace
6
INSTALLATION
Side Wall Clearance
6-1/2" (165mm)
Horizontal Vent Clearances
Top
3"
Side
2"
Bottom
2"
Vertical Vent Clearances 1-1/4" (32mm)
* see mantle clearance instructions
(page 7).
CLEARANCES
The clearances listed below are Minimum dis-
tances unless otherwise stated:
A major cause of chimney related fires is
failure to maintain required clearances
(air space) to combustible materials. It is
of the greatest importance that this fire-
place and vent system be installed only
in accordance with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
NOTE: The minimum floor clearance must
be maintained from the top surface of
the carpeting, tile, etc.
Diagram 1
This includes:
1) Clocking the appliance to ensure the cor-
rect firing rate (rate noted on label 45,000
Btu/h) after burning appliance for 15 min-
utes.
2) If required, adjusting the primary air to
ensure that the flame does not carbon. First
allow the unit to burn for 15-20 min. to
stabilize.
CAUTION: Any alteration to the product
that causes sooting or carboning that
results in damage is not the responsibil-
ity of the manufacturer.
LOCATING YOUR
GAS STOVE
1) When selecting a location for your stove,
ensure that the clearances outlined on this
page are met.
2) Provide adequate clearances for servic-
ing.
3) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, met-
al, concrete). This may be the floor, or
raised up on a platform to enhance its visual
impact. If the appliance is going to be in-
stalled on carpeting, combustible linoleum
tile or other combustible material other than
wood flooring, the appliance must be in-
stalled on a metal or wood panel extending
the full width and depth of the appliance.
4) The P95-2 Direct Vent Gas Fireplace can be
installed in a recessed position or framed
out into the room as in A, B, C, D. See
Diagram 1.
7) We recommend that you plan your installa-
tion on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have a
qualified inspector, dealer, or installer re-
view your plans before installation.
Note: For vent terminations see page
10.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided. See page 29.
5) This appliance is Listed for bedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The P95-2 Direct Vent Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
A)
Flat on Wall
B)
Flat on Wall Corner
C)
Recessed into
Wall/Alcove
D)
Corner
OPTIONAL
DUCT SYSTEM
KIT #946-556
The HeatWave Air Duct Kit increases the
effectiveness of your fireplace by dispersing
warm air from the fireplace to remote locations
in the same room or other rooms in your home.
Up to two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be
operated at one time. This includes the internal
blower option as well.
OPTIONAL
HEAT RELEASE
KIT #946-570
The Heat Release Kit expels warm air from the
fireplace to the outside of the building, allowing
the fireplace to be operated with less heat
entering the room. The kit may be used on either
the left or right side.
WARNING:
Fire hazard is an extreme risk
if these clearances are not
adhered to.
Clearances for HeatWave and
Heat Release Kit
Heat Release Kit
The HeatWave Duct Kit and the Heat Release
Kit have different clearance and framing
requirements, check the HeatWave and Heat
Release manual for details.