Excalibur P95-2 Zero Clearance Direct Vent Gas Fireplace

6

INSTALLATION

Side Wall Clearance

6-1/2" (165mm)

Horizontal Vent Clearances

Top

3"

Side

2"

Bottom

2"

Vertical Vent Clearances 1-1/4" (32mm)

* see mantle clearance instructions
(page 7).

CLEARANCES

The clearances listed below are Minimum dis-
tances unless otherwise stated:

A major cause of chimney related fires is
failure to maintain required clearances
(air space) to combustible materials. It is
of the greatest importance that this fire-
place and vent system be installed only
in accordance with these instructions.

Clearance to Combustibles from:

Back

0"

(0mm)

Side

0"

(0mm)

Floor

0"

(0mm)

NOTE: The minimum floor clearance must
be maintained from the top surface of
the carpeting, tile, etc.

Diagram 1

This includes:

1) Clocking the appliance to ensure the cor-

rect firing rate (rate noted on label 45,000
Btu/h) after burning appliance for 15 min-
utes.

2) If required, adjusting the primary air to

ensure that the flame does not carbon. First
allow the unit to burn for 15-20 min. to
stabilize.

CAUTION: Any alteration to the product
that causes sooting or carboning that
results in damage is not the responsibil-
ity of the manufacturer.

LOCATING YOUR

GAS STOVE

1) When selecting a location for your stove,

ensure that the clearances outlined on this
page are met.

2) Provide adequate clearances for servic-

ing.

3) The appliance must be installed on a flat,

solid, continuous surface (e.g. wood, met-
al, concrete). This may be the floor, or
raised up on a platform to enhance its visual
impact. If the appliance is going to be in-
stalled on carpeting, combustible linoleum
tile or other combustible material other than
wood flooring, the appliance must be in-
stalled on a metal or wood panel extending
the full width and depth of the appliance.

4) The P95-2 Direct Vent Gas Fireplace can be

installed in a recessed position or framed
out into the room as in A, B, C, D. See
Diagram 1.

7) We recommend that you plan your installa-

tion on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have a
qualified inspector, dealer, or installer re-
view your plans before installation.

Note: For vent terminations see page

10.

MANUFACTURED

MOBILE HOME

ADDITIONAL

REQUIREMENTS

1) Ensure that structural members are not cut

or weakened during installation.

2) Ensure proper grounding using the #8

ground lug provided. See page 29.

5) This appliance is Listed for bedroom  instal-

lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.

6) The P95-2 Direct Vent Gas Fireplace is

approved for alcove installations, which
meet the clearances listed on this page.

A)

Flat on Wall

B)

Flat on Wall Corner

C)

Recessed into
Wall/Alcove

D)

Corner

OPTIONAL

DUCT SYSTEM

KIT #946-556

The  HeatWave Air Duct Kit increases the
effectiveness of your fireplace by dispersing
warm air from the fireplace to remote locations
in the same room or other rooms in your home.

Up to  two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be
operated at one time. This includes the internal
blower option as well.

OPTIONAL

HEAT RELEASE

KIT #946-570

The Heat  Release Kit expels warm air from the
fireplace to the outside of the building, allowing
the fireplace to be operated with less heat
entering the room. The kit may be used on either
the left or right side.

WARNING:

Fire hazard is an extreme risk

if these clearances are not

adhered to.

Clearances for HeatWave and

Heat Release Kit

Heat Release Kit

The HeatWave Duct Kit and the Heat Release
Kit have different clearance and framing
requirements, check the HeatWave and Heat
Release manual for details.

Содержание Excalibur P95-LP2

Страница 1: ...appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot rea...

Страница 2: ...urer s installation instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or the current Standard of Fire Safety Criteria for Manufactured Home Installations S...

Страница 3: ...ve 6 ManufacturedHomeAdditionalRequirements 6 Optional HeatWave Duct System 6 Optional Heat Release Kit 6 Clearances 6 CombustibleMantelClearances 7 P95 2 Flat Surround and Tile Kit 7 Unit Base Stand...

Страница 4: ...TE Excalibur units are constantly being improved Check the label on the unit and if there is a difference the label on the unit is the correct one SAFETY LABEL Copy of Safety Decal for P95 2 For the S...

Страница 5: ...building envelope Never vent to another room or inside a building Make sure that the vent is fitted as per Venting instructions 5 Inspect the venting system annually for blockage and any signs of det...

Страница 6: ...ull width and depth of the appliance 4 TheP95 2DirectVentGasFireplacecanbe installed in a recessed position or framed out into the room as in A B C D See Diagram 1 7 We recommend that you plan your in...

Страница 7: ...he fireplace itself These drawings are to scale at 1 6 one inch 6 inches Mantel can be installed anywhere in shaded area or higher using the above scale Note Ensure the paint that is used on the mante...

Страница 8: ...thick the unit must be raised 1 53 3 4 48 3 4 Header C L 21 1 8 533mm 2 1 4 4 2 Gas connection on this side Non combustible Material Combustible Material 11 dia hole through wall for Flex or for DuraV...

Страница 9: ...ore installation Back View of Cover Plate Pin Holes Top Clip Pins 2 Position bottom of cover plate over pins located at the bottom of the firebox Oblong Screw Holes 3 Bring cover plate towards the uni...

Страница 10: ...spring spacers 4 4 thimble 2 5 AstroCap XL termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point Stainless Steel 4 10 vinyl siding standoff If longer run...

Страница 11: ...14 36cm G Clearance to inside corner with AstroCap Termination Cap min 6 15cm with Dura Vent Termination Cap 12 30cm H Not to be installed above a meter regulator assembly within 3 90cm horizontally f...

Страница 12: ...Terminal must not be recessed into siding Measure the wall thickness including furring strips If a Vinyl Siding Standoff is required it must be used with vinyl siding measure to outside surface of wal...

Страница 13: ...1245B 45o Elbow Black 1245G 45o Elbow Swivel 1245BG 45o Elbow Black Swivel 1290 90o Elbow 1290B 90o Elbow Black 1290G 90o Elbow Swivel 1290BG 90o Elbow Black Swivel 5 x 8 Description 5 x 8 Description...

Страница 14: ...Vent pipe Maintain clearances to combustibles as listed on pages 6 to 8 Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A...

Страница 15: ...pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal Please note minimum 1 foot between 90o elbows is required Option V H V V1 H H1 A 0 Min 1 Max 1 Min 2 M...

Страница 16: ...tal pipe length is 30 feet with min of 6 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is re quired For additional vertical venting with 2 x 90o elbows...

Страница 17: ...stibles Note Must use optional flue adapter when using Simpson Dura Vent pipe Part 770 994 VENTING ARRANGEMENTS VERTICAL TERMINATIONS SIMPSON DURA VENT DIRECT VENT GS SYSTEM Propane Natural Gas The sh...

Страница 18: ...ions of straight vertical and offset to vertical terminations with Simpson Dura Vent Direct Vent GS vent systems for Propane and Natural Gas Maximum two 45o elbows allowed Vent must be supported at of...

Страница 19: ...s are designed to slide straight onto the male ends of adjacent pipes and fittings by orienting the four pipe indentations so they match and slideintothefourentryslotsonthemale ends Diagram 1 Push the...

Страница 20: ...at his point Next drop a plumb bob from the roof to the hole previouslydrilledintheceiling andmarkthe spot where the vent will penetrate the roof Determine if ceiling joists roof rafters or other fram...

Страница 21: ...S for FPI Direct Vent System Flex 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit and the electrical Junction block is on the left side on the left Locate th...

Страница 22: ...ssure tap s using a 5 16 ID hose 4 Light the pilot and turn the valve to ON position 5 The pressure check should be carried out with the unit burning and the setting should be within the limits specif...

Страница 23: ...ow behind the orifice Burner Orifice Conversion Kit Contains Qty Part Description 1 910 018 SIT Conversion Kit 50 Turndown LP 1 910 037 LP Injector Pilot Orifice 1 904 431 Burner Orifice 49 1 908 255...

Страница 24: ...g OPTIONAL BRICK PANELS 1 Open the bottom louver door Loosen the 2 screws holding the Burner ON OFF switch and bracket to the bottom louver and lift the assembly out 2 Remove facade 3 Remove glass doo...

Страница 25: ...the top of Log 309 on Log 308 supported by the knot 11 Fit Log 310 on the pin and then swing the front end of the log to hit the first grate tab 12 Place the embers on the front of the burner tray 30...

Страница 26: ...ws from the mounting plate that are on the back of the facade Screw Remove screws from the mounting tabs 4 Slide Bottom Louver into position On each side secure the bottom screw first into the sidebra...

Страница 27: ...sert the new studs through the holes and secure them by first putting on the washer and then tighten with a nut DOUBLE SINGLEDOOROPTION 1 Remove the handles by removing the nut and screw Install the n...

Страница 28: ...nstall into the receptacle box CAUTION Do not connect millivolt wall switch wire to a 120V wire CAUTION Do not connect millivolt remote control wires to a 120V wire Thermostat Wire Table Option 3 WALL...

Страница 29: ...to the receptacle box provided with the unit in case the fan is installed at a later date CAUTION Label all wires prior to disconnection when servicing controls Wiring er rors can cause improper and...

Страница 30: ...aint curing process To ensure that the paint is properly cured it is recommended that you burn your fireplace for at least four 4 hours the first time before you use it with the fan on When first oper...

Страница 31: ...ube s and logs and is made of a different gauge material from the rest of the firebox and body Therefore the varying thick nesses of steel will expand and contract at slightly different rates which ca...

Страница 32: ...xcessive conden sation such as water droplets forming in the inner liner and subsequently dripping out the joints Continuous condensation can cause corrosion of caps pipe and fittings It may be caused...

Страница 33: ...ide with one screw 11 Attach the two control boxes to the bottom unit base and tighten the 2 screws on the left side and 1 screw on the right side 9 Connect the fan ground wire of Fan B and the power...

Страница 34: ...leeves through the brick panel to the firebox base reversing step 8 leaving them about 1 4 6mm above the brick panel Reinstall the rear log stand 12 Install Burner grate assembly 13 Hookupthegaslinean...

Страница 35: ...lts 910 331 P Fan Motor 120 Volts 770 523 Fan Switch Assembly 43 910 813 Power Cord 120 Volts 46 910 330 Fan Speed Control Switch 47 904 586 Knob Speed Control 48 910 199 Wire Holder Clip 49 910 142 T...

Страница 36: ...Excalibur P95 2 Zero Clearance Direct Vent Gas Fireplace 36 PARTS LIST...

Страница 37: ...10 378 Valve S I T Natural Gas 910 380 Valve S I T Propane 58 Valve Bracket 66 910 038 Pilot Assy 3 way flame S I T NG 910 039 Pilot Assy 3 way flame S I T LP 904 660 Orifice 30 Natural Gas 904 431 Or...

Страница 38: ...urround Louver 145 Surround Hood 146 Handle 148 Rivet 67 5 16 x 1 2 157 Carriage Bolt 948 221 Logo Plate 770 931 Double Screen Door Complete Black 770 932 Double Screen Door Complete Nickel 770 933 Do...

Страница 39: ..._________ ______________________________________________________ ______________________________________________________ _______________________________________________________________ ________________...

Страница 40: ..._________ ______________________________________________________ ______________________________________________________ _______________________________________________________________ ________________...

Страница 41: ..._________ ______________________________________________________ ______________________________________________________ _______________________________________________________________ ________________...

Страница 42: ..._________ ______________________________________________________ ______________________________________________________ _______________________________________________________________ ________________...

Страница 43: ...lts or costs of workmanship from unauthorized service persons or dealers At all times FPI reserves the right to inspect product in the field which is claimed to be defective All claims must be submitt...

Страница 44: ...__________________________ Printed in Canada Excalibur fireplace products are designed with relia bility and simplicity in mind In addition our internal Quality Assurance Team carefully inspects each...

Отзывы: