TROUBLESHOOTING

 There is no connection to the PLC

Creating a Tag

 in the eWON500™ 

to check the serial connection

 to the PLC

 

Principles

The first action to take in that case is to validate the connection between the eWON500™ and the 
PLC by means of an eWON variable called a 

Tag

.

Each eWON Tag refers to a Topic in which some defined settings are common to each of the Tags 
which are attached to it.

 

Creating a Tag in the eWON500™

IO server Setup

¤ Go back to the appropriate 

IO Server

 configuration page

¤ Scroll to the bottom from the page, and check the 

Topic A

 

Enabled

 check box

¤ (Special case for the FINS IO server: select 

Fins Serial

 as the 

Protocol

)

¤ Let the 

Poll Rate

 value set to default

¤ 

Update

 the IO server configuration

Tag Setup

¤ Go to the 

Tag Setup

 page. From the Main eWON™ menu: 

Configuration

/

Tag 

Setup

/

Create New Tag

• Tag Name

Any name respecting the eWON syntax (no space, no 
special characters)

• Page

Let 

Default

• Description

Enter here a free text

• Server Name

Select the appropriate Server Name from the scrolling list

• Topic Name

Enter A (the topic that has been configured previously)

• Address

An existing address on the target PLC on the serial link

• Type

Select here the appropriate type for the Tag (

Analog

 or 

Boolean

)

• Force Read 

Only

Validate the checkbox (we will just read the value on the 
PLC)

• eWON value

Let the two fields unchanged

Add/Update Only

 to validate the Tag

Содержание eWON500

Страница 1: ...N500 The Transparent Gateway ver 1 0 9 11 05 User Guide eWON500 is a Multiprotocol Transparent Gateway MODBUS TCP MODBUS RTU EtherNet IP DF1 FINS TCP FINS Hostlink XIP UNITELWAY ISO TCP PPI MPI VCOM P...

Страница 2: ...econtrol tasks through Ethernet The goal of the current document is to teach you how to correctly configure the eWON500 as a Transparent Gateway to address a wide range of various Programmable Logic C...

Страница 3: ...the PLC The eWON500 configurable serial port Depending on the serial link which is supported by the target PLC the eWON500 serial port dip switches left bottom side from the eWON500 when you face its...

Страница 4: ...o Half Duplex Let Master response timeout Rx message timeout and Tx message timeout empty default values applied Let Force Unitelway V2 and Disable 0 254 translation unchecked Set the ADO field to its...

Страница 5: ...cable between your eWON500 and the PLC IO server configuration Go to the MODBUS IO server page Configuration IO Server Config MODBUS Edit Set the Baud Rate Parity and Stop Bit s according to your devi...

Страница 6: ...et the Baud Rate Parity Stop Bit s Frame Error Detection according to your device and HW Mode to Full Duplex Let Master response timeout Rx message timeout and Tx message timeout empty default value a...

Страница 7: ...INS Edit Set the Server Port and FINS TCP server node according to your device let the Routing Entry fields empty Set the Baud Rate Parity Databits Stop Bit s HW Mode and Reply Timeout with the requir...

Страница 8: ...c A Enabled check box Special case for the FINS IO server select Fins Serial as the Protocol Let the Poll Rate value set to default Update the IO server configuration Tag Setup Go to the Tag Setup pag...

Страница 9: ...WON500 embeds a page from which you can directly check the value from the Tags which match an existing word on a device from the serial bus Reading a Tag value in the eWON The Tag s monitoring page di...

Страница 10: ...led s panel A label just close to the panel illustrates the various configurable modes in the eWON500 see illustrated table below Just set up the correct configuration then power OFF power ON the eWO...

Страница 11: ...le issue occurs Moreover information is added to an eWON500 log file when it detects a problem From the Main Menu eWON toolbar click on Diagnostic then on Status and click on the I O server counter yo...

Страница 12: ...nformation by selecting the required Event Class and by choosing the Reporting Level Error Warning or Trace Just don t forget to click on Update to refresh the page when done However if the displayed...

Страница 13: ...m cable can be delivered as accessory to connect Shneider PLCs it has a SUBD9 connector at the eWON side and a MiniDIN connector at the PLC side MiniDIN PIN Schneider Signal Name eWON Signal Name eWON...

Страница 14: ...parent Gateway ver 1 0 9 11 05 Page 14 User Guide 1747 CP3 cable between eWON and SLC 500 pinout The connectors are SUBD9 female at both sides 9 pin eWON 1 2 Rx 3 Tx 4 5 COM 6 7 RTS 8 CTS Table 2 1747...

Страница 15: ...sparent Gateway ver 1 0 9 11 05 User Guide XW2Z S002 cable between eWON and OMRON PLC Pinout 9pin 9pin Dsub Female Dsub Male 3 SD SD 2 2 RD RD 3 7 RS RS 4 8 CS CS 5 5 SG SG 9 eWON NS series PT Table 3...

Отзывы: