background image

This diagram reflects the UZC4 

Fire Alarm Output terminals 

wired to a FIRE ALARM 

System with a Fail Safe, Normally Open Dry Contact. The circuit is normally closed and 
must OPEN to activate the UZC4 FIRE MODE. Be sure to cut the Jumper 1 resistor when 
you interlock the UZC4 to the Fire Alarm System.  When the UZC4 activates Fire Mode, 
the HVAC System will shutdown and all connected dampers will close to Isolate & 
Compartmentalize the HVAC Duct System. The Fire Alarm System must reset to NORMAL  
before the UZC4 will allow HVAC Operations to resume.

SYSTEM WIRING CONTINUED - Specialty Applications

   Using the UZC4’s “FIRE Interlock” Feature to satisfy Building Fire Codes

EWC Controls Inc.   385 Highway 33    Englishtown, NJ 07726   800-446-3110   FAX 732-446-5362      E-Mail- [email protected]

18

NC

NO

C

A
U
X
R
L
Y

E
B
D

O
A

D
M
P
R

M1

M2

M4

M6

M6
M4
M2
M1

M6
M4
M2
M1

RESET

CB1

R
C

24V

24V

FA

FA

MXC

MXR

UZC4

FIRE ALARM
   SYSTEM

NC C NO

CUT

 Separate 24vac 
    Transformer

    To Line Voltage
Provide over current
       protection

The UZC4 has a “FIRE” 
interlock feature that allows 
the UZC4 to satisfy HVAC Fire 
C o d e   i n   R e s i d e n t i a l   &  
C o m m e r c i a l   b u i l d i n g s .  
Coordinate with the Fire 
S y s t e m s   C o n t r a c t o r   t o  
interlock the UZC4 into the 
building Fire Alarm system as 
shown and cut the Jumper 1. 
When properly interlocked to 
the buildings Fire Alarm 
system, the UZC4 becomes 
an integral part of the Fire 
Safety System. If the Fire 
Alarm system activates, the 
UZC4 will shutdown the 
controlled HVAC system and 
force all connected dampers to 
t h e   c l o s e d   p o s i t i o n s ,  
effectively isolating the duct 
work and the Fan system.
This action will reduce the 
spread of smoke advancing 
through the building assisted 
by Fan and Duct systems that 
are not interlocked with a Fire 
Alarm system, or equipped 
with the capability to do so.

The UZC4 has a set of 
dedicated terminals to power 
up and control an (EBD) 
Electronic Bypass Damper. 
The UZC4 will assume control 
of the EBD and force it to the 
OPEN position during the Idle 
periods, Short cycle delays or 
Changeover delays. It will also 
maintain that open position for 
45 seconds at the start of any 
t h e r m o s t a t   d e m a n d   f o r  
Heating, Cooling, or Fan only 
operation. After 45 seconds 
the UZC4 will release control 
of the EBD, resulting in a 
smooth gradual increase in 
static pressure. The 45 second 
s t a r t u p   d e l a y   a l l o w s   a  
Constant speed fan to start in a 
“Quiet Mode” eliminating air 
noise upon system startup. It 
also eliminates hunting on 
variable speed systems and it 
enhances the latent cooling 
capacity of any HVAC system.

Field Wiring =

Factory Wiring = 

4

6

1

WHITE “COMMON” WIRE

NC

NO

C

Pressure Control
Wiring Compartment

“EBD” Motor

WIRE

NUT

GREEN

RED

Using the UZC4’s  “ON BOARD BYPASS DAMPER SUPPORT”

Wire up the “EBD” straight to the UZC4 to obtain integrated Bypass Damper operational 
support via the UZC4’s bypass firmware. The UZC4 defaults the bypass damper open 
during idle periods and releases control to the EBD 45 seconds after the Fan starts. This 
action results in a smooth, quiet startup and gradual increase in static pressure.

UZC4

JMP1

Figure 29.

Figure 30.

Содержание Ultra-Zone UZC4

Страница 1: ...ool Changeover Status LED System LEDs Damper LEDs Operating Power Manual and Automatic Thermal Circuit Breakers Operating Conditions Indoor Fan Control Model UZC4 Zone Control TB 221 Box Contents UZC4 Zone Control Panel Supply Air Sensor Technical Bulletin TB221 Mounting Hardware Leave this bulletin on the job site for future reference EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3...

Страница 2: ...he SYSTEM RESET button for 5 seconds That will reset the Main Expansion modules on a UZC4 Zoning System NOTE A three minute startup delay occurs whenever the CPU Reset button is pushed upon any initial power up or when a power failure has occurred Timer Reset BUTTON CPU Reset BUTTON Emergency Heat Switch Supply Return Air Limit Delay Timer 3 minutes Fixed Opposite Mode Delay Timer A 20 minute dela...

Страница 3: ...Alarm Interlock feature will over ride the CO2 Monitor feature AUXILARY or DeHUMIDIFY INTERFACE RELAY Enhanced Comfort Solution Auxiliary dry SPDT output This feature is affected by Heat Cool Operations Fire Alarm Activation Over rides this feature The UZC4 includes an Auxiliary Interface Input and SPDT action Dry Contact Output This allows the Installer to connect various Auxiliary controls such ...

Страница 4: ...set points If the Return Air temperature is 80 degree F or below Stage Up is allowed 105 degree F or above Stage Down is forced Default 10 set points If the Return Air temperature is 90 degree F or below Stage Up is allowed 115 degree F or above Stage Down is forced RETURN AIR LIMITS DURING HEATING CYCLES FOR GAS OIL STRAIGHT ELECTRIC Default 0 set points If the Return Air temperature is 80 degree...

Страница 5: ...tem being controlled the type of thermostats connected and the programmed staging sequence you desire As always you can still control a multi stage HVAC system using inexpensive single stage thermostats and sequence the staging by on board adjustable time delay or by using an optional outdoor air sensor OAS and sequence the staging via an outdoor air set point You can still control a state of the ...

Страница 6: ...s to the correct and or desired positions will result in improper operation of the controlled HVAC System Please read and study the entire Technical Bulletin and if necessary Call the EWC Technical Support Hotline when assistance is required Leave this Technical Bulletin with the Home or Building Owner for future reference 6 EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732...

Страница 7: ... always over ride the Timer or OAS staging operations Unless the 50 rule has been enabled or the Return Air temperature limit has been exceeded NOTE4 Thermostatic demands to Stage Down will be honored unless the Timer is also in use NOTE5 Disable the Timer by setting to OFF and the UZC4 will obey Stage up Stage down demands via the thermostats only OAS STAGES TMR OFF 50 RULE ON Select OFF if you d...

Страница 8: ...mber of zones rounded up must be calling for the same mode of operation or the UZC4 will not activate the HVAC system This feature only activates at 8 or more zones Select OFF if you do not want to utilize the Zone Demand Limiter feature NOTE Zone 1 is not affected by this feature Zone 1 demands are always honored ZDL example A zone system has 20 total zones and the ZDL feature is active At least ...

Страница 9: ...ring Supply All of the preceding diagrams reflect conventional Non Heat Pump thermostats controlling conventional HVAC systems However the equipment being controlled does not have to be the conventional type A heat pump system can be controlled using conventional thermostats Figure 5 Figure 4 Model EWT 725 Configured for typical 2 stage Gas or Electric heating system with 1 stage cooling C W2 Y2 R...

Страница 10: ... Thermostat instructions for further details Model EWT 955WH Wireless Thermostat Configured for 3 heat 2 cool heat pump See thermostat instructions for further details Model EWT 855i Configured for 3 heat 2 cool See thermostat instructions for further details Model EWT 725 Configured for 2 heat 1 cool heat pump See thermostat instructions for further details Field installed jumper Field installed ...

Страница 11: ...TAT W1 E Y2 AUX R CO2 CO2 Wiring for typical 3 stage Heat 2 stage cool Heat Pump Diagram reflects De humidification terminal wired to the Auxilary input For auxilary output wiring see page 14 Auxilary Relay Dip Switch 5 Bank 2 should be set to Reverse Acting RA Refer to Dehumidify Operations on page 14 Wiring a split circuit thermostat to operate a Radiant floor heating or Baseboard heating Hydron...

Страница 12: ...ontrol or Zone Valve or Pump Control Terminals Y C R Y G C TYPICAL FAN CENTER TERMINAL BLOCK OUTDOOR CONDENSING UNIT W W RC RH LINK RC RH LINK Cut Rc Rh Jumper Cut Rc Rh Jumper Note Your Air Handler may include a W terminal That means it may have it s own isolation circuit If you can confirm this simply connect the W1 terminal to the W terminal on the air handler Do not cut the Rc Rh jumper Wire u...

Страница 13: ...efer to Mfr s data for specific equipment dip switch settings and logical program settings Set up the UZC4 to control the staging based on Time with single stage Conventional Thermostats Or you can install 3 stage Heat Pump Thermostats on all zones High Efficiency Heat Pump 3 or 4 Stage Heat and 2 Stage Cool Warning All of the wiring diagrams provided are general in nature and may not perfectly ma...

Страница 14: ...control calls for Dehumidification the UZC4 will activate Y1 G and the Auxiliary Relay to signal the Air Handler to slow the fan down The UZC4 WILL ALSO e n e r g i z e t h e E Emergency output terminal to REHEAT the cold discharge air and Rapidly Dehumidify the home Energizing the E during this cycle prevents over cooling the home A common Customer complaint with the DeHumidify cycle in these HVA...

Страница 15: ...trol the fan speed on most any variable speed air handlers or furnaces during cooling operations The UZC4 will lower the fan speed when 25 or less of the total zones are calling for cooling When this occurs the UZC4 will activate the Auxiliary relay output which will de energize the DS BK terminal on the Forced air unit resulting in the blower running at a lower speed NOTE 1 A jumper is required a...

Страница 16: ...uxiliary Feature can be used to control Humidify Operations on any HVAC System Set the Auxiliary relay Dip Switch to Direct Acting and connect a dry contact Humidity Control to the R and AUX R terminals When the UZC4 detects a demand to Humidify it w i l l e n e r g i z e t h e Auxiliary Output Relay The Auxiliary relay contacts are dry so you can connect and control most any humidifier you want T...

Страница 17: ... UZC4 to a separate CO2 Monitor with auxilary dry contacts as shown Also install and wire up a fresh air damper as shown Set the PPM trip threshold on the CO2 Monitor per the Mfr s Instructions or local requirements Upon activation the UZC4 will open the Fresh Air Damper and Start the Indoor Fan if it is not already running The UZC4 will continue the ventilation process until the CO2 Monitor reset...

Страница 18: ... will shutdown the controlled HVAC system and force all connected dampers to t h e c l o s e d p o s i t i o n s effectively isolating the duct work and the Fan system This action will reduce the spread of smoke advancing through the building assisted by Fan and Duct systems that are not interlocked with a Fire Alarm system or equipped with the capability to do so The UZC4 has a set of dedicated t...

Страница 19: ...SE DIAGRAMS PRIOR TO INSTALLATION AND POWER WIRING DOING SO WILL SAVE TIMEAND LABOR ON THE JOB SITE Patented Optical Damper Motor Actuators Figure 31 Figure 33 Figure 34 All Models SMDL BMDL Damper Wiring 2 4 1 M1 M2 M4 M6 All Models MA ND MA URD Damper Wiring 4 6 1 Patented Optical Damper Motor Actuators Figure 32 M1 M2 M4 M6 On all these dampers and most older style dampers including competitor ...

Страница 20: ...block and allows a maximum 60va transformer to be connected This means that you can directly connect a theoretical maximum of 12 Genuine ND URD dampers to a single 2 zone expansion module Now you no longer have to isolate power up multiple dampers using field installed relays The Expansion modules provide the isolation for you See the diagram below for typical wiring solutions for dampers Separate...

Страница 21: ... R8 D14 D13 D12 D11 R15 R12 R13 R14 D16 D15 R17 R16 R18 R63 R55 R53 R52 R54 R61 R60 Z1 R56 R57 R19 C2 C54 D2 R20 R21 R22 A U X R L Y C25 C26 C27 R65 R66 R67 R68 R71 R70 R69 R72 R73 R28 R27 R26 R25 R24 R23 D17 D18 D19 D20 D21 D22 R64 C48 C47 C46 C51 C50 C49 C52 SW3 R134 R128 R129 R130 R130 R132 R133 R135 R127 R126 R125 R124 R123 R122 U17 U18 U19 C42 C41 C40 C45 C44 C43 R121 R120 R119 R118 R117 R116...

Страница 22: ...EN LED will illuminate solid to indicate that the Outside Air damper is energized open in response to the CO2 detector or other device to provide demand based ventilation BYPASS DMPR The BYPASS DMPR LED will illuminate solid to indicate that the Bypass damper s is being forced to the Open position Occurs during idle short cycle and changeover periods AUX RELAY The AUX RELAY LED will illuminate sol...

Страница 23: ...Damper Motor Power Input Block The ZXM2 Expansion Module is powered via the Bus Cable from the UZC4 but the power for the dampers must be provided by a separate transformer and is isolated from the module This allows great freedom to connect as many dampers as the 2 5 amp thermal breaker can handle See page 19 for damper motor power supply details Make sure to read the ZXM2 Technical Bulletin for ...

Страница 24: ... on the UZC4 and other ULTRA ZONE products When calling for Technical Support please have a multi meter pocket screwdriver and wire cutter stripper handy TECHNICAL SUPPORT LED s do not illuminate and HVAC system does not respond LED s are not responding properly and HVAC system is malfunctioning LED S are responding properly but HVAC system is malfunctioning SYMPTOM Disconnect the wire s from the ...

Отзывы: