DEPOLOX® Pool Compact
5. Installation
45
EN
5.12.1 Electrical installation electronics
module
1 Open the housing cover of the electronics
module.
2 Connect the power supply in accordance
with the wiring diagram (chapter 9.).
3 Installing a retrofit kit (optional) for mA
outputs or Redox or conductivity (chapter
5.14).
4 Wire the CPU-board in accordance with
wiring diagram chapter 9. and Ansteue-
rung chapter 5.12.2.
5 Fit the housing cover.
6 Then put the DEPOLOX® Pool Compact
into operation (chapter 5.13).
5.12.2 pH safety deactivation on control
of dosing pumps
For safe operation, we recommend that you
switch off the dosing pump for chlorine and if
appropriate pH by means of an alarm contact
that is configured as a pH Min alarm and pH
Max alarm. This means the chlorine and pH
dosing switches off automatically in the event
of a fault so as to prevent an impermissible
dosing of chemicals.
Fig. 10 Plan of terminal assignment
NOTICE
•
The electronics module is not suitable
for electrical connection with perman-
ently installed cable conduits.
•
If the cable glands do not meet local ins-
tallation rules and regulations, these
glands must be replaced with suitable
ones.
•
The electronics module is equipped with
a flexible voltage supply input and
accepts AC voltages from 100 to 240
volts. Take the power consumption into
account when dimensioning (chapter
3.8).
WARNING
Risk of injury or damage to the device!
•
The DEPOLOX® Pool Compact is not
equipped with a mains switch and is in
operation as soon as the supply voltage is
applied. For this reason, an external
switch or circuit breaker with a clearly
identifiable “Off” switch position is
necessary.
•
Line cross-section for the mains input
side at least 0.75 mm² (AWG 18), on-site
mains fuse 6 A with 100 to 240 V AC sup-
ply.
•
When connecting system components
(e.g. devices, motors, pumps) as well as
when entering operating data, the sys-
tem components must be switched off in
order to prevent uncontrolled activation
or incorrect operation.
•
If devices are connected to the internal
voltage supply (e.g. dosing devices) or via
fixed connection cables (e.g. connectors),
the total power consumption must not
exceed 6 A.
NOTICE
Note the correct polarity of the voltage con-
nections and the correct dimensioning of
the wire cross-sections (chapter “3.8 -
Power consumption).
NOTICE
Make sure that all cable glands are installed
correctly.
54
55
56
N
L1
65
64
63
DEPOLOX Pool Compact
dosing pump
N L1
external power supply
F4
T3
,15A
F7
T3
,15A
K5
K2