5. Installation
DEPOLOX® Pool Compact
46
EN
1 Make the following alarm contact settings
on the DEPOLOX® Pool Compact:
2 In addition, we recommend you make the
following settings:
•
Setting of the limit values:
•
Activation of the "Safety deactivation
Cl2" function so as to prevent uncon-
trolled dosing of chemicals.
5.13 Startup
Following complete mechanical and electrical
installation, initial commissioning can be car-
ried out. Please check that the following con-
ditions are met:
•
Electronics module and flow cell are
installed.
•
Electrode cleaning sand is filled.
•
Housing covers are fitted.
•
Optional strainer is installed.
•
Sample water inlet and outlet are connec-
ted.
•
Sensors are installed in the flow cell.
•
The sensors are connected to the electro-
nics module.
•
The electronics module is wired in accor-
dance with the wiring diagram (circuit dia-
gram) and local regulations.
•
Ensure that all transport protection was
removed.
•
Check all connections for leakage.
•
Sample water monitoring and circulation
monitoring are active (chapter 3.5.7).
Alarm 2 assignment
pH Min 1, pH Max 1, if
appropriate also Chlo-
rine Max 1
Acknowledge
withour
Delay time
0:00:00 h
Relay
K5
Reax function
Normally closed
contact
NOTICE
If the pH Min limit value is undershot, the
pH Max limit value is exceeded or, if appro-
priate, if the Chlorine Max limit value is
exceeded then the dosings are switched off.
pH Min 1
pH 6.5
pH Max 1
pH 7.6
Chlorine Max 1
0.7 mg/l
DANGER
Risk of injury or death!
The DEPOLOX® Pool Compact must not be
operated with flammable liquids.
ATTENTION
Risk of injury or damage to the device!
•
To ensure safe and correct commissio-
ning, knowledge of the operation, con-
nected electrical load, measurement
signals, cable assignment and fuse pro-
tection of the connected devices and
machines and the relevant safety regula-
tions is required.
•
Startup of the DEPOLOX® Pool Compact
may therefore only be performed by
qualified and authorized electricians.
ATTENTION
Risk of injury or damage to the device!
•
Incorrectly connected devices can be
damaged, possibly irreparably, or cause
faults in other equipment when they are
switched on or in operation.
•
Ensure that the measuring and control-
cables are not confused or make contact
with one another.
•
Never connect or disconnect any cables
to which voltage is applied.
WARNING
Risk of injury or damage to the device!
When connecting the DEPOLOX® Pool Com-
pact to the power supply, a 6A back-up fuse
must be used in the mains supply line.