5. Installation
DEPOLOX® Pool Compact
48
EN
5.14 Installing retrofit kits/extensions
5.14.1 4-way mA output card
1 Disconnect the electronics module from
the power supply.
2 Remove the housing cover of the electro-
nics module.
3 Install mA output card at position A and
make sure that the holders engage. Note
the correct installation direction.
4 Plug in terminal block at position B.
5 Wire in accordance with the wiring dia-
gram (chapter 9.).
6 Fit the housing cover.
7 Connect the power supply again.
8 The electronics module automatically
detects the installed modules and enables
the corresponding settings menus.
9 Configure mA outputs as required.
10 Check all menu settings and configure if
necessary.
Fig. 11 View, installation of the 4-way mA
output card
5.14.2 ORP sensor measuring module
1 Disconnect the electronics module from
the power supply.
2 Remove the housing cover of the electro-
nics module.
3 Feed the ORP (Redox) sensor cable
through the cable gland together with the
pH sensor cable with double sealing
insert.
4 Connect sensor cable to the ORP (Redox)
sensor card (A).
5 Insert sensor card into Mod1 slot (B).
Ensure that the holders engage. Rout the
sensor cable upward and around the sen-
sor module to the cable gland.
6 Remove the cover of the flow cell.
7 Install ORP (Redox) sensor in the flow cell.
Please remove the blind plug first (note
position!).
8 Feed the sensor cable through the hole at
the bottom into the housing of the flow
cell and route upward to the sensor.
9 Connect sensor cable to the ORP (Redox)
sensor.
10 Fit the housing cover.
11 Switch the device on.
12 Calibrate the ORP sensor.
13 Set the limit values and perform ORP set-
tings.
Fig. 12 Section ORP sensor module with sen-
sor cable in slot
A ORP (Redox) sensor card
B
Mod1 slot
DANGER
Risk of injury or death!
External voltages may still be connected
even if the operating voltage is switched off.
NOTICE
After changes the electronics module resets
all parameter to factory settings.
A
B
NOTICE
The sensor card is automatically detected
and the ORP measurement is displayed.
A
B