Page
43
Parameters and their default values (factory setting):
Parameter
Default
Notes
1.
Precoat Cycle Time
10 minutes
Time system is in the closed precoat
loop.
2.
Effluent Valve Close Delay
0 seconds
Time after bump is initiated to close
the effluent valve.
3.
Regen Valve Open to Precoat Time
5 seconds
Time display on the screen prior
Opening Precoat Valve to start of
Precoat Timing.
4.
Pump Run Confirm Time
5 seconds
Time the control enclosure waits for a
closed contact from the pump motor
starter. If the closed contact signal is
not received, the system shuts down.
5.
Effluent Valve to Bump Start Time
5 seconds
Delay to start bump after the effluent
valve closes.
6.
Regen Valve Close Delay
15 seconds
Delay time between the effluent relay
energizing to effluent valve opening
after the precoat cycle and the regen
relay de-energizes to close the regen
valve.
7.
Regen Valve Open Delay
5 seconds
Delay time for the regen valve relay to
energize to open the regen valve once
the start button is pressed.
8.
Fireman Off Before Effluent Valve
Open
0 seconds
Delay time after precoat before the
effluent valve opens.
9.
Fireman On to Effluent Valve Close
Time
0 seconds
Set to the desired delay, if used. Relay
energizes when an automatic or
manual bump is initiated and shutoff
auxiliary equipment. System does not
bump until the delay times out.
10.
Bump Set Off Time
5 seconds
Time bump solenoid de-energizes
when
Bump Set
is pressed.
11.
Bump Set On Time
2 seconds
Time bump solenoid energizes when
Bump Set
is pressed.
12.
Bump Auto/Man Off Time
5 seconds
Time bump solenoid de-energizes
when an automatic or manual bump is
initiated.
13.
Bump Auto/Man On Time
2 seconds
Time bump solenoid is energized.
14.
Flex Clean (Flexible Tube Chemical
Cleaning) Loop Time
120 seconds
Time that the pump is on in precoat
mode during chemical cleaning. Set to
0
if using Neptune-Benson Chem
Clean Express.
15.
Flex Clean (Flexible Tube Chemical
Cleaning) Loop Delay
15 minutes
Delay time between system idle to
bumping and precoating, as in
Parameter 14.
16.
Auto Bump Loops
10
Number of bumps, when initiated.
17.
Required Bump Passcode
OFF
When set to
ON
, bump cannot be
initiated without a passcode.
Содержание DEFENDER SP-27-48-487
Страница 14: ...Page 14 General Installation Schematic ...
Страница 15: ...Page 15 DIMENSIONAL REFERENCE Standard Defender ...
Страница 16: ...Page 16 Assero Defender Reduced Height Defender ...
Страница 17: ...Page 17 Reduced Height Defender ...
Страница 72: ...Page 72 Figure 33 Alarm History Screen CLEAR HISTORY Clears all alarm and warning messages from the system ...
Страница 77: ...Page 77 APPENDIX ...
Страница 78: ...Page 78 Electrical Schematic ...
Страница 79: ...Page 79 Head Loss Curve ...