18
Input / Output Dock
USB Port
A USB port is available to download the data log of the optional SilverPoint local
temperature monitoring to a USB memory device. You will use the USB port to
download and clear the data log when the storage is full. The USB port is also used to
update the firmware. Verify that the port is intact by inserting the USB drive (not
included) and looking for the USB icon in the icon bar at the top of the LCD display.
Data Monitoring Backup Battery
Activating the Battery
The included battery is shipped with a protective tab so that its power does not
drain. To activate it you must remove the tab from its location inside the I/O
Dock panel.
Replacing the Battery
1.
Open the I/O Dock panel
2.
Remove and replace the battery with only type CR123A
3.
Close the I/O Dock panel
Battery Monitoring and Maintenance
This battery backs up the data monitoring system only. It does not run the
cooling system of the refrigerator. The monitoring system is designed to display
an alert when the battery drops below 30% remaining capacity.
The battery serves to support continuous temperature monitoring during
power outages and will need to be replaced periodically.
When replacing the battery, replace only with a CR123A or IEC16340 type
battery.
We recommend that you keep spare batteries on-hand. This battery will
allow you to continue to monitor internal temperature even in the event of a
power outage.
This battery will not power the refrigeration. You must ensure uninterrupted
power to the refrigerator and monitoring system at all times.